![Mitsubishi Electric MELSEC iQ-R-R00CPU Скачать руководство пользователя страница 307](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-r00cpu/melsec-iq-r-r00cpu_user-manual_239139307.webp)
16 MULTIPLE CPU SYSTEM FUNCTION
16.4 Data Communication Between CPU Modules
305
16
Communication through refresh
The device data for each CPU module is written/read only by the parameter settings. Using refresh areas allows data
communication between all or a part of the CPU modules in the multiple CPU system, thereby enabling devices of other CPU
modules to be used by the host CPU module.
Types of refresh
The following table shows the types of refresh.
*1 The fixed scan communication area is refreshed on the cycle specified in the fixed scan communication setting.
*2 Refresh fails if the multiple CPU synchronous interrupt program (I45) does not exist on the program.
The following figure shows the timing of each refresh.
Refresh timing
Application
Memory to be used
At the END processing
For data communication of devices in synchronization with the scan
CPU buffer memory
At the execution of multiple CPU
synchronous interrupt program
(I45)
For data communication of devices at the period specified in the fixed scan
communication setting
Fixed scan communication area
END
END
:
:
:
:
0.888ms
0.888ms
0.888ms
0.888ms
Refresh with the CPU buffer memory (set)
Refresh with the CPU buffer memory (read)
Refresh with the fixed scan communication area (read)
Refresh with the fixed scan communication area (set)
Sequence scan
Program
Multiple CPU
communication
cycle
Cycle that is set for the multiple CPU communication cycle setting
Time
1 scan
1 scan
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......