7 PARAMETER SETTINGS
7.2 Basic Setting
Transmission points
Set the number of transmission points of AnyWireASLINK.
Startup operating mode
Set whether to read the parameters of slave modules at start-up of the FX5-ASL-M.
Double verification
Set the double verification of the FX5-ASL-M.
*1 The word double verification be selected from until 1st word up to until 15th word.
Error status automatic recovery
Set whether to automatically recover the FX5-ASL-M from the error status.
Item
Description
Setting range
Transmission points setting (IN)
Set the number of input transmission points.
One transmission cycle time is determined by setting the number
of transmission points. (
Page 85 Transmission cycle time)
• 0 input points
• 8 input points
• 16 input points
• 24 input points
• 32 input points
• 48 input points
• 64 input points
• 80 input points
• 96 input points
• 128 input points
• 160 input points
• 192 input points
• 224 input points
• 256 input points
(Default: 256 input points)
Transmission points setting (OUT)
Set the number of output transmission points.
One transmission cycle time is determined by setting the number
of transmission points. (
Page 85 Transmission cycle time)
• 0 output points
• 8 output points
• 16 output points
• 24 output points
• 32 output points
• 48 output points
• 64 output points
• 80 output points
• 96 output points
• 128 output points
• 160 output points
• 192 output points
• 224 output points
• 256 output points
(Default: 128 output points)
Item
Description
Setting range
Startup operating mode setting
Set the operation mode at start-up. (
Information Acquisition at Start-up Function)
• Without slave information acquisition
• Get slave information acquisition
(Default: Without slave information acquisition)
Item
Description
Setting range
Double verification mode setting
Set the double verification mode. (
• All points, double verification of bit
• Double verification of word (16 bit), until 1st word
• All points, double verification of word (16 bit)
(Default: All points, double verification of bit)
Item
Description
Setting range
Error status automatic recovery
mode setting
Set the error status automatic recovery mode. (
Status Automatic Recovery Function)
• No error status automatic recovery
• Error status automatic recovery
(Default: No error status automatic recovery)