*1 Does not apply to FX

3UC

-16MT/ .

*2 X000 to X017 use adjustable digital filter values.

When setting the input filter for X000 to X005 to 5

µ

s or

capturing pulses of a 50 to 100kHz response frequency with a
high speed counter, wire the terminals as stated below.

- The wiring length should be 5m (16’4”) or less.
- Connect a bleeder resistor of 1.5k

 (1W or more) to the

input terminal, so that the sum of the load current of the
open collector transistor output on the connected device
and the input current of the main body is 20mA or more.

3.3.2

Handling of input terminal

1) FX

3UC

-

MT/D, FX

2NC

-

EX(-T)

Inputs turn ON when the input terminal and COM terminal are
electrically connected with a no-voltage contact or NPN open
collector transistor

2) FX

3UC

-

MT/DSS, FX

2NC

-

EX(-T)-DS

sink input
Inputs turn ON when the 24V DC

 terminal and COM

U

 terminal 

are connected, and the input terminal and 24V DC

 terminal are 

electrically connected with a no-voltage contact or NPN open 
collector transistor.

source input
Inputs turn ON when the 24V DC

 terminal and COM

U

 terminal 

are connected, and the input terminal and 24V DC

 terminal are 

electrically connected with a no-voltage contact or PNP open 
collector transistor.
Where 

U

 indicates:0 to 2

3.3.3

Example of input wiring

1. Examples of input wiring (FX

3UC

-

MT/D)

*1 The grounding resistance should be 100

 or less.

2. Examples of sink input wiring (FX

3UC

-

MT/DSS)

*1 The grounding resistance should be 100

 or less.

*2 In FX

3UC

-64MT/DSS or FX

3UC

-96MT/DSS units, the COM0,

COM1 and COM2 terminals are not connected internally. Wire
the COM0, COM1 and COM2 terminals respectively.

3. Examples of source input wiring (FX

3UC

-

MT/DSS)

*1 The grounding resistance should be 100

 or less.

*2 In FX

3UC

-64MT/DSS or FX

3UC

-96MT/DSS units, the COM0,

COM1 and COM2 terminals are not connected internally. Wire
the COM0, COM1 and COM2 terminals respectively.

Operation display

LED on panel turns ON when photocoupler is
driven.

Item

Input specification(24V DC)

 +

 

-

 

-

 +

24V DC

FX

3UC

-

††

MT/D

Fuse

Class D

grounding

*1

Breaker, Circuit protector,

Fuse, etc.

COM

X000

X001

X002

Three

wire

sensor

NPN

COM

FX

2NC

-

††

EX(-T)

COM

X000

COM

-

+

-

+

24V DC

FX

3UC

-

††

MT/DSS

Fuse

Breaker, Circuit protector,

Fuse, etc.

COM0

X000

X001

X002

COM0

FX

2NC

-

††

EX(-T)-DS

COM0

X000

COM0

*2

*2

Class D

grounding

*1

Three

wire

sensor

NPN

-

+

24V DC

FX

3UC

-

††

MT/DSS

Fuse

COM0

X000

X001

X002

COM0

FX

2NC

-

††

EX(-T)-DS

COM0

X000

COM0

*2

*2

Class D

grounding

*1

Breaker, Circuit protector,

Fuse, etc.

Three

wire

sensor

PNP

-

+

3.4

Output specifications and example of external 
wiring

For more details, refer to the FX

3UC

 Series User's Manual -

Hardware Edition

3.4.1

Transistor output specifications

*1 When using an instruction related to pulse train output or

positioning, make sure to set the load current to 10 to 100mA 
(5 to 24V DC).

*2 The transistor OFF time is longer under lighter loads.

For example, under a load of 24V DC 40mA, the response time
is approx. 0.3ms. When response performance is required
under light loads, provide a dummy resistor to increase the load
current.

3.4.2

Handling of transistor output circuit

Output terminal:

The main unit and FX

2NC

 input/output extension block have 16

transistor output points per common.
Two COM  or +V

U

 terminals connected to each other inside the

PLC are provided for outputs.
Connect two COM  or +V

U

 terminals outside the PLC so that the

load applied to each COM  or +V

U

 terminal is smaller.

Where   indicates:1 to 3
Where 

U

 indicates:0 to 2

Output current

The ON voltage of the output transistor is approx. 1.5V. When
driving a semiconductor element, carefully check the input voltage
characteristics of the applied element.

3.4.3

Example of transistor output wiring

1. Examples of sink output wiring

2. Examples of source output wiring

Item

Output specification 

(Transistor)

Number of output points

FX

3UC

-16MT/D(SS) 8 

points

FX

3UC

-32MT/D(SS) 16 

points

FX

3UC

-64MT/D(SS) 32 

points

FX

3UC

-96MT/D(SS) 48 

points

FX

2NC

-16EYT(-DSS) 16 points

FX

2NC

-32EYT(-DSS) 32 points

Output connecting type

connector

Output form

FX

3UC

-

MT/D

FX

2NC

-

EYT

Sink

FX

3UC

-

MT/

DSS
FX

2NC

-

EYT

-DSS

Source

External power supply

5 to 30V DC

Max.
load

Resis-
tance
load

Main
units

Y000 to
Y003

0.3A/point

Make sure that the 
total load current 
of 8 resistance 
load points is 0.8A 
or less.

Y004 or
more

0.1A/point

FX

2NC

-

EYT

(-DSS)

0.1A/point

Induc-
tive
load

Main
units

Y000 to
Y003

7.2W/point
(24V DC)

Make sure that the 
total load of 16 
inductive load 
points is 38.4W/
24V DC or less.

Y004 or
more

2.4W/point
(24V DC)

FX

2NC

-

EYT

(-DSS)

2.4W/point (24V DC)

Open circuit leakage current

0.1mA or less/30V DC

Resp
onse
time

OFF

ON

Main
units

Y000 to

Y002

5

µ

s or less/10mA or more 

(5 to 24V DC)

*1

Y003 
or more

0.2ms or less/100mA or more 
(at 24V DC)

*2

FX

2NC

-

EYT

(-DSS)

0.2ms or less/100mA or more 
(at 24V DC)

ON

OFF

Main
units

Y000 to

Y002

5

µ

s or less/10mA or more 

(5 to 24V DC)

*1

Y003 
or more

0.2ms or less/100mA or more 
(at 24V DC)

*2

FX

2NC

-

EYT

(-DSS)

0.2ms or less/100mA or more 
(at 24V DC)

Circuit insulation

Photocoupler insulation

Display of output operation

LED on panel turns ON when
photocoupler is driven.

COM1

COM1

Y000

Y001

Y002

24V

DC

Load

Load

Load

Fuse

Emergency

stop

FX

3UC

-

††

MT/D

FX

2NC

-

††

EYT

+V0

+V0

Y000

Y001

Y002

FX

3UC

-

††

MT/DSS

FX

2NC

-

††

EYT-DSS

24V

DC

Load

Load

Load

Fuse

Emergency

stop

Содержание MELSEC FX3U-485ADP-MB

Страница 1: ...the PLC is transported with the BAT LED on or the battery exhausted the battery backed data may be unstable during transportation The PLC is a precision instrument During transportation avoid impacts larger than those specified in Section 2 1 Failure to do so may cause failures in the PLC After transportation verify the operations of the PLC STARTUP AND MAINTENANCE PRECAUTIONS Models MELSEC FX2N s...

Страница 2: ...e standard Radiated Emissions Mains Terminal Voltage Emissions RF immunity Fast Transients ESD Surge Voltage drops and interruptions Conducted Power magnetic fields Standard Remark IEC1010 1 1990 A1 1992 BSEN61010 1 1993 Safety requirements for electrical equipment for measurement control and laboratory use General requirements The equipment has been assessed as a component for fitting in a suitab...

Страница 3: ...eries terminal blocks Battery and memory cassettes Notes When a dust proof sheet is supplied with an extension unit block keep the sheet applied to the ventilation slits during installation and wiring work To prevent temperature rise do not install the PLC on a floor a ceiling or a vertical surface Install it horizontally on a wall as shown in section 2 2 Keep a space of 50mm 1 97 or more between ...

Страница 4: ... lower connector when performing crossover wiring for the later block In case of the FX2NC EX T DS removal of the connector cover is unnecessary Black Black Red Red Green Ground a Press here Self made power cable To use self made power cables use the following wire and connector suggestions 2 5 Connection to input output connector The input output connectors of the Main units conform to MIL C 8350...

Страница 5: ...put output wiring 50 to 100m 164 1 to 328 1 long will cause almost no problems of noise but generally the wiring length should be less than 20m 65 7 to ensure the safety Extension cables are easily affected by noise Lay the cables at a distance of at least 30 to 50mm 1 19 to 1 97 away from the PLC output and other power lines Item Specification Supply voltage 24V DC 20 15 1 Ripple Voltage p p 5 or...

Страница 6: ...ing For more details refer to the FX3UC Series User s Manual Hardware Edition 3 4 1 Transistor output specifications 1 When using an instruction related to pulse train output or positioning make sure to set the load current to 10 to 100mA 5 to 24V DC 2 The transistor OFF time is longer under lighter loads For example under a load of 24V DC 40mA the response time is approx 0 3ms When response perfo...

Страница 7: ...rve simultaneous ON ratio 80 55 C Ambient temperature applicable 20 45 C When extension blocks units are connected Supply voltage 24V DC 40 C 60 65 When only the main unit is used without extension blocks units 3 5 3 Cautions on relay output wiring For more details refer to FX3UC Series User s Manual Hardware Edition 1 Protection circuit for load short circuits A short circuit at a load connected ...

Страница 8: ... Y2 Y3 Y4 Y5 Y6 Y7 V1 V1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 OUT Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 V0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Lower Notch Upper IN X0 X1 X2 X3 X4 X5 X6 X7 COM COM COM X0 X1 X2 X3 X4 X5 X6 X7 COM Lower Upper OUT Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM1 COM1 COM2 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM2 Lower Upper This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent ...

Отзывы: