*1 Does not apply to FX
3UC
-16MT/ .
*2 X000 to X017 use adjustable digital filter values.
When setting the input filter for X000 to X005 to 5
µ
s or
capturing pulses of a 50 to 100kHz response frequency with a
high speed counter, wire the terminals as stated below.
- The wiring length should be 5m (16’4”) or less.
- Connect a bleeder resistor of 1.5k
Ω
(1W or more) to the
input terminal, so that the sum of the load current of the
open collector transistor output on the connected device
and the input current of the main body is 20mA or more.
3.3.2
Handling of input terminal
1) FX
3UC
-
MT/D, FX
2NC
-
EX(-T)
Inputs turn ON when the input terminal and COM terminal are
electrically connected with a no-voltage contact or NPN open
collector transistor
2) FX
3UC
-
MT/DSS, FX
2NC
-
EX(-T)-DS
•
sink input
Inputs turn ON when the 24V DC
terminal and COM
U
terminal
are connected, and the input terminal and 24V DC
terminal are
electrically connected with a no-voltage contact or NPN open
collector transistor.
•
source input
Inputs turn ON when the 24V DC
terminal and COM
U
terminal
are connected, and the input terminal and 24V DC
terminal are
electrically connected with a no-voltage contact or PNP open
collector transistor.
Where
U
indicates:0 to 2
3.3.3
Example of input wiring
1. Examples of input wiring (FX
3UC
-
MT/D)
*1 The grounding resistance should be 100
Ω
or less.
2. Examples of sink input wiring (FX
3UC
-
MT/DSS)
*1 The grounding resistance should be 100
Ω
or less.
*2 In FX
3UC
-64MT/DSS or FX
3UC
-96MT/DSS units, the COM0,
COM1 and COM2 terminals are not connected internally. Wire
the COM0, COM1 and COM2 terminals respectively.
3. Examples of source input wiring (FX
3UC
-
MT/DSS)
*1 The grounding resistance should be 100
Ω
or less.
*2 In FX
3UC
-64MT/DSS or FX
3UC
-96MT/DSS units, the COM0,
COM1 and COM2 terminals are not connected internally. Wire
the COM0, COM1 and COM2 terminals respectively.
Operation display
LED on panel turns ON when photocoupler is
driven.
Item
Input specification(24V DC)
+
-
-
+
24V DC
FX
3UC
-
MT/D
Fuse
Class D
grounding
*1
Breaker, Circuit protector,
Fuse, etc.
COM
X000
X001
X002
Three
wire
sensor
NPN
COM
FX
2NC
-
EX(-T)
COM
X000
COM
-
+
-
+
24V DC
FX
3UC
-
MT/DSS
Fuse
Breaker, Circuit protector,
Fuse, etc.
COM0
X000
X001
X002
COM0
FX
2NC
-
EX(-T)-DS
COM0
X000
COM0
*2
*2
Class D
grounding
*1
Three
wire
sensor
NPN
-
+
24V DC
FX
3UC
-
MT/DSS
Fuse
COM0
X000
X001
X002
COM0
FX
2NC
-
EX(-T)-DS
COM0
X000
COM0
*2
*2
Class D
grounding
*1
Breaker, Circuit protector,
Fuse, etc.
Three
wire
sensor
PNP
-
+
3.4
Output specifications and example of external
wiring
→
For more details, refer to the FX
3UC
Series User's Manual -
Hardware Edition
3.4.1
Transistor output specifications
*1 When using an instruction related to pulse train output or
positioning, make sure to set the load current to 10 to 100mA
(5 to 24V DC).
*2 The transistor OFF time is longer under lighter loads.
For example, under a load of 24V DC 40mA, the response time
is approx. 0.3ms. When response performance is required
under light loads, provide a dummy resistor to increase the load
current.
3.4.2
Handling of transistor output circuit
Output terminal:
The main unit and FX
2NC
input/output extension block have 16
transistor output points per common.
Two COM or +V
U
terminals connected to each other inside the
PLC are provided for outputs.
Connect two COM or +V
U
terminals outside the PLC so that the
load applied to each COM or +V
U
terminal is smaller.
Where indicates:1 to 3
Where
U
indicates:0 to 2
Output current
The ON voltage of the output transistor is approx. 1.5V. When
driving a semiconductor element, carefully check the input voltage
characteristics of the applied element.
3.4.3
Example of transistor output wiring
1. Examples of sink output wiring
2. Examples of source output wiring
Item
Output specification
(Transistor)
Number of output points
FX
3UC
-16MT/D(SS) 8
points
FX
3UC
-32MT/D(SS) 16
points
FX
3UC
-64MT/D(SS) 32
points
FX
3UC
-96MT/D(SS) 48
points
FX
2NC
-16EYT(-DSS) 16 points
FX
2NC
-32EYT(-DSS) 32 points
Output connecting type
connector
Output form
FX
3UC
-
MT/D
FX
2NC
-
EYT
Sink
FX
3UC
-
MT/
DSS
FX
2NC
-
EYT
-DSS
Source
External power supply
5 to 30V DC
Max.
load
Resis-
tance
load
Main
units
Y000 to
Y003
0.3A/point
Make sure that the
total load current
of 8 resistance
load points is 0.8A
or less.
Y004 or
more
0.1A/point
FX
2NC
-
EYT
(-DSS)
0.1A/point
Induc-
tive
load
Main
units
Y000 to
Y003
7.2W/point
(24V DC)
Make sure that the
total load of 16
inductive load
points is 38.4W/
24V DC or less.
Y004 or
more
2.4W/point
(24V DC)
FX
2NC
-
EYT
(-DSS)
2.4W/point (24V DC)
Open circuit leakage current
0.1mA or less/30V DC
Resp
onse
time
OFF
→
ON
Main
units
Y000 to
Y002
5
µ
s or less/10mA or more
(5 to 24V DC)
*1
Y003
or more
0.2ms or less/100mA or more
(at 24V DC)
*2
FX
2NC
-
EYT
(-DSS)
0.2ms or less/100mA or more
(at 24V DC)
ON
→
OFF
Main
units
Y000 to
Y002
5
µ
s or less/10mA or more
(5 to 24V DC)
*1
Y003
or more
0.2ms or less/100mA or more
(at 24V DC)
*2
FX
2NC
-
EYT
(-DSS)
0.2ms or less/100mA or more
(at 24V DC)
Circuit insulation
Photocoupler insulation
Display of output operation
LED on panel turns ON when
photocoupler is driven.
COM1
COM1
Y000
Y001
Y002
24V
DC
Load
Load
Load
Fuse
Emergency
stop
FX
3UC
-
MT/D
FX
2NC
-
EYT
+V0
+V0
Y000
Y001
Y002
FX
3UC
-
MT/DSS
FX
2NC
-
EYT-DSS
24V
DC
Load
Load
Load
Fuse
Emergency
stop