8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS
8.1 Self Diagnostics Function
Operation upon error occurring
The product operating status and LED status will differ depending on the type of error generated.
For error types, see the following page.
Operation upon error detection setting
Set operation settings upon error detection.
MELIPC operation upon error detection setting
Configure the operation of this product when a problem is detected by using "MELIPC operation upon error detection setting"
of "RAS Setting".
Window
[Basic Parameter]
[RAS Setting]
[MELIPC Operation Setting at Error Detected]
Displayed items
*1 If "Shutdown" is selected, the operation upon error detection is the same as when the SHUTDOWN switch is pressed. (
*2 If the Windows part continuously restarts, a window to select whether to start Windows in safe mode is displayed.
*3 If "Do not restart" is selected, the error code is recorded in the event history at error detection, the MAIN ERR LED is lit, and the WIN
RDY LED is off.
If "Restart" is selected, the Windows part is restarted at error detection, and an event stating it restarted automatically is saved in the
event history.
For details on the internal configuration of this product (Windows part and VxWorks part), refer to the following
manual.
MELIPC MI5000 Series User's Manual (Startup)
Precautions
■
Automatic restart at a Windows system error
If Windows automatic restart is enabled, and 'Restart' is selected for when the Windows part stops, this product may restart
repeatedly. If 'Restart' is selected, disable Windows automatic restart.
Windows Start
[Windows System Tools]
[Control Panel]
[System and Security]
[System]
[Advanced system
settings]
[Advanced]
[Startup and Recovery]
[Settings]
[System failure]
[Automatically restart]
■
If the MELIPC temperature error settings are "Shut down"
The product may not shut down if MI Configurator or programs that make file accesses are operating, or depending on the
status of Windows.
Item
Description
Setting range
MELIPC temperature error
Set the device operation upon detection of a Main module temperature
error.
If "Shutdown" is set, the VxWorks part and Windows part shut down when
an error is detected.
• Shut down
• Do not shut down
(Default: Shutdown)
Windows part stop
Set operation of the Windows part when a stop state is detected due to a
Windows blue screen including timeout detection from the Windows part
system watchdog timer or other issue.
• Do not restart
• Restart
(Default: Do not restart)
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......