10
1.
Display and Button Functions of Each Parts
Part names
Operation buttons (For details, refer to page 12.)
LCD with backlight
Current Input terminals
+C1, C1: Input a circuit current.
+C2, C2: Input a circuit current.
+C3, C3: Input a circuit current.
MODBUS
®
RTU communication terminal
T/R+: MODBUS
®
RTU communication transmission terminal
T/R-: MODBUS
®
RTU communication transmission terminal
SG: Signal Ground.
Ter: Termination terminal
(120 Ω termination when short-circuited to the terminal T/R-)
SLD: Shielded wire terminal (Ground resistance 100 Ω or less)
Voltage Input terminals
P1, P2, P3, PN: Input a circuit voltage.
Auxiliary power input terminals
MA, MB: Connect to an auxiliary power.
: Ground terminal
(Ground resistance: 100 Ω or less)
Terminal cover
■Front view
■Rear view (main unit)