PIPE CONNECTION

1. Indoor unit connection

• Connect both liquid and gas piping to the indoor unit.

- Apply a thin coat of refrigerant oil on the seat surface

of pipe.

- For connection first align the center, then hand tighten

the first 3 to 4 turns of flare nut.

- Use tightening torque table below as a guideline for

the indoor unit side union joint section, and tighten us-
ing two wrenches. Excess tightening damages the
flared section.

Pipe diameter

Tightening torque

mm

N·m

kgf·cm

6.35

13.7 to 17.7

140 to 180

15.88

73.5 to 78.4

750 to 800

2. Outdoor unit connection

• Connect pipes to stop valve pipe joint of the outdoor unit in

the same manner applied for the indoor unit.

- For tightening, use a torque wrench or spanner, and

use the same tightening torque applied for the indoor
unit.

3. Refrigerant pipe insulation

• Use pipe cover (foam polyethylene 8 mm thickness) which

is contained in accessories, insulate both liquid and gas
pipes together. Put the refrigerant piping and apply piping
tape 

C

.

a

Indoor unit refrigerant pipe

b

Flare joint

d

Pipe cover

A

Refrigerant pipe

C

Piping tape

4. Knockout cover

• Attach knockout cover 

9

 to close knockout hole to prevent

rat or something strange from getting into the indoor unit.

9

Knockout cover

0

Screw for 

9

 4 

×

 10 mm

A

b

a

c

d

c

9

0

Connecting wire and
refrigerant pipes
must be separated.

6-4

PURGING PROCEDURES · LEAK TEST

• Use the vacuum pump for air purging for the purpose of environmental protection.

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor and the outdoor unit.

Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe. (The stop valve will
not work in it initial state fresh out of the factory (totally closed with cap on).)

Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas
pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the vacuum
pump.

Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve remains in the same
position. Confirm that the pressure gauge shows–0.101 Mpa [Gauge] (–760 mmHg).

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and
liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Pipe length up to 7 m

No gas charge is needed.

Pipe length exceeding 7 m

Charge the prescribed amount of

gas. (refer to 3)

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

Tightening torque

N·m

kgf·cm

Cap for service port

13.7 to 17.7

140 to 180

Cap for stop valve

19.6 to 29.4

200 to 300

*Close

*Open

Hexagonal wrench

Stop valve

*4 to 5 turns

Stop valve

(or the vacuum pump with
the function to prevent the
back flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose
(for R410A)

Vacuum
pump

Adapter for preventing the
back flow

Charge hose
(for R410A)

Service port

Stop
valve

Содержание MCFH-A24WV

Страница 1: ...SHOULD ALWAYS BE OBSERVED FOR SAFETY 2 2 SELECTING THE INSTALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNIT INSTALLATION 9 6 INDOOR OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN 10 7 FOR MOVEMENT AND MAINTENANCE 13 English ...

Страница 2: ... 3 In rooms where inverter type fluorescent lamps are used the signal from the wireless remote controller may not be received 2 3 OUTDOOR UNIT Where it is not exposed to strong wind Where airflow is good and dustless Where it is not exposed to rain and direct sunshine Where neighbours are not annoyed by operation sound or hot air Where rigid wall or support is available to prevent the increase of ...

Страница 3: ...TO BE PROVIDED AT YOUR SIDE Item Q ty A Refrigerant pipe 1 set B Indoor outdoor connecting wire 2 core 1 0 mm2 1 C Piping tape 1 D Drain pipe PVC pipe OD ø26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5 F Fixing screw for E The quantity depends on the pipe length 2 to 5 G Drain joint pipe PVC pipe OD ø26 L 50 mm 1 H Power supply cord 2 I Piping hole repa...

Страница 4: ...erature and humidity conditions may cause paper pattern to shrink or expand Measure dimensions before drilling holes 2 Suspension structure Give site of suspension strong struc ture Wood structure Select tie beam one story houses or second floor girder two story houses as reinforcement member Use sturdy beams of at least 60 mm square for beam pitch of 900 mm or less or of at least 90 mm square for...

Страница 5: ...ation only Front grille Knockout hole Knockout hole for drain pipe Unit fixing screw 2 Unit fixing screw 2 Hanging bolt Be sure to set hanging bolt in this position to keep unit s inclination LATES e fixing bolts plate fixing bolts J f installation plates ght one way direction stallation plates 1 door unit ve the ceiling put t a spring washer double nut Fig 3 orward the ceiling olt through the in ...

Страница 6: ...tion plate 1 FRONT 4 2 6 FIXING UNIT TO INSTALLATION PLATES 1 Suspending unit from installation plate Hoist unit so that hanging bolt 4 on the sides of unit fit into holes in installation plate 1 2 Securing unit to installation plates Be sure to tighten unit fixing screw 2 to unit securely 4 3 KNOCKOUT COVER After removing the knockout holes attach knockout cover 9 on the knockout hold edge shown ...

Страница 7: ...the terminal block securely so that no stress is applied to the connecting section of the terminal block Incomplete connection or fixing of the wire could result in a fire When connecting the power supply cord to the power supply source be sure to connect each wire to the correct pole Be sure to connect the Live wire side to the L terminal and connect the Neutral conductor side to the N terminal 4...

Страница 8: ... D tilts downward 1 100 or more on outdoor side drain side and no traps or heaving exist When the drain pipe D is relatively long provide support metal fixtures midway to eliminate waving Odor trap at the end of drain pipe D is not required a Insulation b Supporting metal fixture c Downward inclination of 1 100 or more d Air bleeder e Do not raise f Odor trap g The end of drain hose is immersed in...

Страница 9: ...th Design 245 IEC 57 m2 or more in conformity with Design 245 IEC 57 m2 or more in conformity with Design 245 IEC 57 1 0 mm2 in conformity with Design 245 IEC 57 Power supply cord H screw event them from loosening confirm that they do not move Service panel Fixing screws Warning Be sure to attach the service panel of the outdoor unit securely If it is not attached correctly it could result in a fi...

Страница 10: ...ll burrs from the cut cross section of pipe Put the end of the copper pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the piping Copper pipe Good No good Tilted Uneven Burred 3 Putting nut on Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal not possible to put them on after flaring work Flare nut for R4...

Страница 11: ...e then close the gauge manifold valve and stop the vacuum pump Leave as it is for one or two minutes Make sure the pointer gauge manifold valve remains in the same position Confirm that the pressure gauge shows 0 101 Mpa Gauge 760 mmHg Remove the gauge manifold valve quickly from the service port of the stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on bo...

Страница 12: ...rk as the power button of the remote controller is off To prevent breaker off due to the rush of starting current systematize other home appliance not to turn on at the same time 6 7 EXPLANATION TO THE CUSTOMER Using the instruction manual explain the following to the customer how to control temperature how to re move the air filters how to remove or put the remote controller in the remote control...

Страница 13: ... liquid phase of the gas cylinder s phase composition change may occur in the refrigerant In this case ability of the refrigerating cycle decreases or wever charging the liquid refrigerant all at once may cause ge the refrigerant slowly der warm the gas cylinder with warm water under 40 C during m Union Liquid pipe Gas pipe Stop valve Service port Gauge manifold valve for R410A Charge hose for R41...

Страница 14: ...FICE MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 8310 TELEX J24532 CABLE MELCO TOKYO intended for use in the residential al environment on Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Отзывы: