Setting when MA remote controller is connected
●Setup of an refrigerant address
●Setup of Room temperature detector position
●Setting when P series is mixed in the same group (only when running group operation using the MA remote controller)
Functions
SW No.
Operating details
P series is mixed in
the same group
SW500-1: OFF
• Set to OFF when P series is not mixed in the same group.
SW500-1: ON
• Set to ON when P series is mixed in the same group.
SW No.
Refrigerant address
Comments
SW580
Address can be set from 0 to 15 • Set the refrigerant address of the unit that supplies electric power to the MA
remote controller to “0.”
• When carrying out group operation of two of more room air conditioners, set
different refrigerant addresses within the group.
*A to F of the rotary switch correspond to refrigerant addresses 10 to 15.
Functions
SW No.
Operating details
Room temperature
detector position
SW500-2: OFF
• Temperature detected by suction temperature sensor of the unit is made to
be room temperature.
SW500-2: ON
• Temperature detected by temperature sensor of the remote controller is
made to be room temperature.
SW500
ON
OFF
1
2
3
4
SW500
ON
OFF
1
2
3
4