![Mitsubishi Electric Lossnay LGH-200RVXT-E Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/mitsubishi-electric/lossnay-lgh-200rvxt-e/lossnay-lgh-200rvxt-e_technical-manual_241037011.webp)
( 11 / 14 ) N15HHGT0033
6.2 How to set Night-purge from the remote controller (PZ-61DR-E)
From <STEP 1> to <STEP 4> are the same as the technical manual of LGH-RVX-E.
<STEP 5> Night-purge setting 4) Time span for memorizing
Set one of conditions for Night-purge start, time span for memorizing the threshold of outdoor temperature.
For example;
If Lossnay unit operates every day, please set “24 hrs (factory setting)”.
If Lossnay unit stop during weekend, please set “72 hrs” so that Lossnay can start Night-purge in the Monday morning.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-61DR-E
Setting
check
Time span for memorizing
SW No.
Setting
Function No.
Setting Data
N/A
-
-
33
0
(Factory setting)
24 hrs
-
-
1
48 hrs
-
-
2
72 hrs
7.2.5 Reference of heater capacity
Quick reference for heater capacity calculation for each model.
When heater capacity is calculated with fan speed 2
[kW]
Model
LGH-150RVXT-E
LGH-200RVXT-E
LGH-250RVXT-E
Air flow rate m
3
/h
750
1000
1250
Heater
capacity
Target OA temp. increase 5K
1.25
1.67
2.08
Target OA temp. increase 10K
2.50
3.33
4.17
When heater capacity is calculated with fan speed 3
[kW]
Model
LGH-150RVXT-E
LGH-200RVXT-E
LGH-250RVXT-E
Air flow rate m
3
/h
1125
1500
1875
Heater
capacity
Target OA temp. increase 5K
1.88
2.50
3.12
Target OA temp. increase 10K
3.75
5.00
6.25
When heater capacity is calculated with fan speed 4
[kW]
Model
LGH-150RVXT-E
LGH-200RVXT-E
LGH-250RVXT-E
Air flow rate m
3
/h
1500
2000
2500
Heater
capacity
Target OA temp. increase 5K
2.50
3.33
4.17
Target OA temp. increase 10K
5.00
6.67
8.33
2. Lossnay Remote Controller (PZ-43SMF-E)
⑮
[FILTER] Button
Press twice to reset the filter sign display while the Lossnay unit is operating.
Caution: Even when the centralized controller (AE-200E or other) which has filter reset function is connected, please reset while the
Lossnay unit is operating.
CHAPTER
3
Remote controller
Revised information
Содержание Lossnay LGH-200RVXT-E
Страница 2: ... 2 14 N15HHGT0033 Product Part ...
Страница 9: ... 9 14 N15HHGT0033 Control Part ...
Страница 14: ... 14 14 N15HHGT0033 ...
Страница 16: ......