![Mitsubishi Electric LMAP04-E Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/mitsubishi-electric/lmap04-e/lmap04-e_installation-manual_237945007.webp)
5
Indoor[1]-[50]
Network Variables
nv1n
nviOnOff_n
SNVT_switch
nv2n
nvoOnOff_n
SNVT_switch
nv3n
nviMode_n
SNVT_hvac_mode
nv4n
nvoMode_n
SNVT_hvac_mode
(*8)
nv5n
nviSetP_n
SNVT_temp_p
nv6n
nvoSetP_n
SNVT_temp_p
(*8)
(*9)
nv7n
nviCoolSetP_n
SNVT_temp_p
nv8n
nvoCoolSetP_n
SNVT_temp_p
(*9)
(*9)
nv9n
nviHeatSetP_n
SNVT_temp_p
nv10n
nvoHeatSetP_n
SNVT_temp_p
(*9)
(*9,10,11)
nv11n
nviAutoSetP_n
SNVT_temp_p
nv12n
nvoAutoSetP_n
SNVT_temp_p
(*9,10,11)
nv19n
nviFanSpeed_n
SNVT_switch
nv20n
nvoFanSpeed_n
SNVT_switch
(*2,3,4)
nv21n
nviProOnOff_n
SNVT_switch
nv22n
nvoProOnOff_n
SNVT_switch
(*2,3,4)
(*2,3,4)
nv23n
nviProMode_n
SNVT_switch
nv24n
nvoProMode_n
SNVT_switch
(*2,3,4)
(*2,3,4)
nv25n
nviProSetP_n
SNVT_switch
nv26n
nvoProSetP_n
SNVT_switch
(*2,3,4)
(*5)
nv27n
nviThermoOff_n
SNVT_switch
nv28n
nvoThermoOff_n
SNVT_switch
(*5)
(*6)
nv29n
nviFiltReset_n
SNVT_switch
nv30n
nvoOnTime_n
SNVT_time_hour
(*6)
nv31n
nvoSpaceTemp_n
SNVT_temp_p
nv32n
nvoAlarm_n
SNVT_switch
nv33n
nvoErrCode_n
SNVT_count
nv34n
nvoErrAdrs_n
SNVT_count
nv35n
nvoThermoSt_n
SNVT_state
nv36n
nvoThermo_n
SNVT_switch
nv38n
nvoIcMdlSize_n
SNVT_count
nv39n
nvoGroupNo_n
SNVT_count
(*7)
Notes
*1: “n” of the network variable shows M-NET address of indoor units.
*2: It may be unable to be used by the system configuration of indoor units.
*3: It is possible to use with an “MA or ME” remote controller.
*4: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting “OFF”)
*5: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting “OFF”)
*6: For the use of this function, turn ON the switch(SW1-4) on LM ADAPTER.(Factory setting “OFF”)
*7: It is possible to use with other system controller.
*8: This function is available only for the conventional indoor units which don't support the dual setpoint.
*9: These functions are available for the indoor units which support the dual setpoint.
*10: This function is available for the DOAS was manufactured in October, 2012 or later, when it uses with the DOAS.
*11: This function is available when the auto mode should be controlled by single set point like the conventional one.
Group Number
Model Code
Thermo On/Off State
Thermo On/Off State
Local Prohibit On/Off
Local Prohibit Mode
Local Prohibit SetPoint
Error Address
Error Code
Alarm State
Indoor Temperature State
Filter Sign
Thermostat Off
On/Off
Mode
Set Point from network
(Both cool and heat)
Set Point from network
(cooling)
Set Point from network
(heating)
Set Point from network
(auto)
Fan Speed
2-5 Network Variable Specification
The following are applied to the CITY-MULTI type indoor unit of the Multiple split type air conditioners CITY
MULTI.
When Mr.SLIM, LOSSNAY, or Air To Water is used, please refer to the “Network Variable Specification” in
details. Please contact your dealer to obtain the XIF file and the Network Variable Specification.