Installation and operation manual
KSGD02 Revision: 1.4
Page 11 of 16
R
KSGD-01WS-B
3. Operation
When power is applied, a green LED will flash (GREEN/RED)
approximately 5 minutes the green LED will be illuminated permanently and the detector is fully
operational. When a refrigerant leak alarm is detected the LED will flash RED/AMBER, the buzzer will
sound and the relay(s) will change status. The alarm cannot be acknowledged or muted and the
LED/buzzer will indicate an alarm until the refrigerant concentration subsides. In the event of a faulty
sensor the LED will flash RED with an AMBER pulse, the relay(s) will change state and the buzzer will
pulse once a minute. This action will continue until the fault is rectified.
3.1 Operational matrix
Operating State
Dual Relay version
Connection
terminal states
Single Relay version
Connection
terminal states
LED
Buzzer
Gv
Voltage
Power removed
3 & 4
5 & 6
3 & 4
4 & 5
OFF
OFF
N/A
OPEN
CLOSED
OPEN
CLOSED
Warmup (5 minutes)
3 & 4
5 & 6
3 & 4
4 & 5
Flashing
GREEN
>
RED
(1Hz)
OFF
N/A
CLOSED
OPEN
CLOSED
OPEN
Normal operation
3 & 4
5 & 6
3 & 4
4 & 5
Constant
GREEN
OFF
0.4>1VDC*
CLOSED
OPEN
CLOSED
OPEN
Sensor fault
3 & 4
5 & 6
3 & 4
4 & 5
RED
>OFF (1Hz)
1 x
AMBER
FLASH
PER MINUTE
Pulses
once per
minute
<0.1VDC
OPEN
CLOSED
OPEN
CLOSED
As the gas concentration increases
Pre-alarm Level 1;
Reading> ~500ppm
For > 2 seconds
3 & 4
5 & 6
3 & 4
4 & 5
Flashing
GREEN
>OFF (2Hz)
OFF
>2.5VDC
CLOSED
OPEN
CLOSED
OPEN
Pre-alarm Level 2;
Reading> ~1000ppm
For > 2 seconds
3 & 4
5 & 6
3 & 4
4 & 5
Flashing
RED
>OFF (2Hz)
OFF
>3.5VDC
CLOSED
OPEN
CLOSED
OPEN
Low Level Alarm;
Reading> ~1000ppm
For > 30 minutes
3 & 4
5 & 6
3 & 4
4 & 5
Flashing
RED
>
AMBER
(2Hz)
Pulses
2Hz
>3.5VDC
OPEN
CLOSED
OPEN
CLOSED
High Level Alarm;
Reading> ~4000ppm
For > 30 seconds
3 & 4
5 & 6
3 & 4
4 & 5
Flashing
RED
>
AMBER
(4Hz)
Pulses
4Hz
>4.2VDC
OPEN
CLOSED
OPEN
CLOSED
After auto reset (gas leak cleared)
After 60 seconds
delay
3 & 4
5 & 6
3 & 4
4 & 5
Constant
GREEN
OFF
<2.0VDC
CLOSED
OPEN
CLOSED
OPEN
*In normal operation in clean air the Gv voltage should be within the range given, however the detector will remain in
the normal state until the Gv reaches 2V. If the Gv voltage is greater than 1V, the sensor maybe contaminated or detecting
residual refrigerant or contaminant gas / vapor.
PPM Levels quoted are approximate levels expected for R410a refrigerant.