2-1. FIXING OF INSTALLATION PLATE
• Find a structural material (such as a stud) in the wall and fix installation plate (1) hori-
zontally by tightening the fixing screws (2) firmly.
• To prevent installation plate (1) from vibrating, be sure to install the fixing screws in
the holes indicated in the illustration. For added support, fixing screws may also be
installed in other holes.
• When the knockout is removed, apply vinyl tape to the knockout edges to prevent
damaging the wires.
• When bolts recessed in the concrete wall are to be utilized, secure installation plate (1)
using 11 × 20 · 11 × 26 oval hole (450 mm pitch).
• If the recessed bolt is too long, change it for a shorter one available in the market.
2-2. WALL HOLE DRILLING
1) Determine the wall hole position.
2) Drill a ø 75 mm hole. The outdoor side should be
5 to 7 mm lower than the indoor side.
3) Insert wall hole sleeve (C).
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate
1
(2)
Installation plate fixing screw
4 × 25 mm
7
(3) Remote controller holder
1
(4)
Fixing screw for (3) 3.5 × 16 mm
(Black)
2
(5) Battery (AAA) for (6)
2
(6) Wireless remote controller
1
(7)
Felt tape
(For left or left-rear piping)
1
<Outdoor unit>
(8) Drain socket
1
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*1
1
(B) Extension pipe
1
(C) Wall hole sleeve
1
(D) Wall hole cover
1
(E) Pipe fixing band
2 to 5
(F) Fixing screw for (E) 4 × 20 mm
2 to 5
(G) Piping tape
1
(H) Putty
1
(I)
Drain hose
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
1 or 2
(J) Refrigeration oil
1
(K) Power supply cord*1
1
Liquid pipe
Gas pipe
Felt tape (7)
Indoor/outdoor unit
connecting wire (A)
Piping tape (G)
2. INDOOR UNIT INSTALLATION
Level
140 mm
or more
149 mm
or more
55 mm or
more/ 118
mm
or more
for left and
left back piping
(using spacer)
12
mm
or more
1-4. INSTALLATION DIAGRAM
Units should be installed by licensed contractor
according to local code requirements.
Indoor unit
Wall hole
sleeve (C)
Cut off the
extra length.
Pipe fixing band
(E)
Be sure to use wall hole
sleeve (C) to prevent
indoor/outdoor connecting
wire (A) from contacting
metal parts in the wall and
to prevent damage by
rodents in case the wall is
hollow.
Wall hole cover (D)
Seal the wall hole
gap with putty (H).
Fix the pipe to wall
with pipe fixing
band (E).
Fixing screw
(F)
After the leak test, apply
insulating material tightly
so that there is no gap.
When the piping is to be at-
tached to a wall containing
metals (tin plated) or metal
netting, use a chemically
treated wooden piece 20
mm or thicker between the
wall and the piping or wrap
7 to 8 turns of insulation vi-
nyl tape around the piping.
To use existing piping, per-
form COOL operation for
30 minutes and pump down
before removing the old air
conditioner. Remake flare
according to the dimension
for new refrigerant.
Appearance of the outdoor unit may differ from
some models.
Indoor terminal block
Indoor/outdoor
unit
connecting wire
(A)
Outdoor terminal block
Earth wire
(green/yellow)
• For future servicing, give extra length to the
connecting wires.
• Make earth wire a little longer than others. (More
than 60 mm)
• Do not fold the excess wire, or cram it into small
space. Take caution not to damage the wires.
• Be sure to attach each screw to its correspond-
ent terminal when securing the cord and/or the
wire to the terminal block.
Note:
Do not place the wires between the in-
door unit and the installation plate (1). Damaged
wire could cause heat generation or fire.
Wall
Outdoor
side
ø 75 mm
5-7 mm
4) Loosen terminal screw, and connect first the earth wire, then indoor/outdoor unit con-
necting wire (A) to the terminal block. Be careful not to make mis-wiring. Fix the wire
to the terminal block securely so that no part of its core is appeared, and no external
force is conveyed to the connecting section of the terminal block.
5) Firmly tighten the terminal screws to prevent them from loosening. After tightening, pull
the wires lightly to confirm that they do not move.
6) Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA clamp.
Never fail to hook the left claw of the VA clamp. Attach the VA clamp securely.
Installation plate (1)
Center of
ø 75 mm hole
140 mm
or more
149 mm
or more
55 mm or more
118
mm or more for left and left
back piping (using spacer)
Ceiling
Wall
Wall
Fixing screw (2)
* Same for left hole.
Insert
the
scale. *
Align the
scale with
the line. *
100 mm
Terminal block
Fixing screw
Indoor/outdoor unit
connecting wire (A)
VA clamp
Lead wire
15 mm
35 mm
(8)
(I)
Drain piping for outdoor unit
• Provide drain piping before indoor and
outdoor piping connection.
• Connect drain hose (I) I.D.15 mm as
shown in the illustration.
• Make sure to provide drain piping with
a downhill grade for easy drain flow.
Air inlet
Air outlet
Outdoor unit installation
2/4-10 mm × 21mm slot
840 mm
175 mm
500 mm
390 mm
330 mm
349-371 mm
40 mm
100 mm
or more
350 mm
or more
100 mm
or more
500 mm
*3
or more
Note:
Install the unit horizontally.
Do not use drain socket (8) in cold regions. Drain may freeze and
make the fan stop.
The outdoor unit produces condensate during the heating operation.
Select the installation place to ensure to prevent the outdoor unit
and/or the grounds from being wet by drain water or damaged by
frozen drain water.
2-3. CONNECTING WIRES FOR INDOOR UNIT
You can connect indoor/outdoor lead wire without removing the front panel.
1) Open the front panel.
2) Remove VA clamp.
3) Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit and proc-
ess the end of the wire.
2-4. PIPE FORMING AND DRAIN PIPING
Pipe Forming
• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not heaved or snaked.
• Do not pull the hose when applying the tape.
• When the drain hose passes the room, be sure to wrap
insulation material (obtainable at a store) around it.
IMPORTANT NOTES
To comply with the requirements of Australian standard AS/NZS 3000
electrical installations (wiring rules), the electrical wiring required
between the indoor and outdoor units must be installed by a licenced
electrical contractor.
Note:
*1 Place indoor/outdoor unit connecting wire
(A) and power supply cord (K) at least 1
m away from the TV antenna wire.
*3 When any 2 sides of left, right and
rear of unit are clear
clear *2
*2 500 mm or more when front and
sides of unit are clear