13 - 20
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13.4.4 Connection to C Controller
module (MELSEC iQ-R
Series)
This section describes the settings of the GOT and C
Controller module (MELSEC iQ-R Series) in the following
case of system configuration.
Use CW Configurator for the C Controller module
(MELSEC iQ-R Series) communication settings.
POINT
POINT
POINT
CC-Link module (MELSEC iQ-R Series)
For details of the CC-Link module (MELSEC iQ-R
Series), refer to the following manual.
Manuals of MELSEC iQ-R Series
System configuration
*1
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0".
Module parameter setting of CW
Configurator
(1) [Module parameter] of CW Configurator
(a) Module parameter
: Necessary : As necessary : Not necessary
*1
Adjust the settings with GOT settings.
(b) Link refresh setting
: Necessary : As necessary : Not necessary
<CC-Link module>
*1
Type
: Master station
Station No.
: Station No. 0
Mode
: Remote net (Ver.2 mode)
All connect count
: 2
Transmission speed : 156kbps
<GOT (Ver.1 compatible)>
(Use default value for settings other than the following.)
Station type
: Intelligent device
station
Station No.
: Station No. 1
Number of stations
occupied
Exclusive station 1
:
:
Transmission speed
156kbps
(Use default value for settings other than the following.)
<GOT (Ver.2 compatible)>
(Use default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No. 2
Number of stations
occupied
Exclusive station
:
Expanded cyclic setting
Single
:
:
Transmission speed
156kbps
■
[Controller Setting] of GT Designer3
■
Module parameter setting of CW Configurator
Item
Set value
Setting
necessity at
GOT
connection
Station type
Master station
Mode
Remote net (Ver.2
mode)
Station No.
0 (fixed)
Transmission speed
*1
156kbps
Channel No.
(Use default value)
Item
Set value
Setting
necessity at
GOT
connection
Remote input (RX) refresh
device
Set as necessary.
Remote output (RY) refresh
device
Remote register (RWr)
refresh device
Содержание GT15
Страница 2: ......
Страница 34: ...A 32 ...
Страница 92: ......
Страница 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Страница 134: ...3 24 3 ACCESS RANGE FOR MONITORING 3 7 Connection to the Head Module of CC Link IE Field Network System ...
Страница 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Страница 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Страница 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Страница 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Страница 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Страница 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Страница 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Страница 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Страница 510: ......
Страница 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Страница 668: ......
Страница 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Страница 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Страница 714: ......
Страница 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Страница 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Страница 762: ......
Страница 860: ...REVISIONS 4 ...
Страница 863: ......