4. INSTALLATION PROCEDURE
The installation procedure for the CC-Link IE communication unit is
explained using the GT1575.
(1) Power off the GOT.
(2) Remove two extension unit covers of the GOT.
(3) Attach the extension interface relay board to the extension interface 2 on
the GOT.
After the installation, detach the connector cover from the extension
interface relay board.
For the following GOT types, the extension interface relay board is not
needed.
•GT1655,GT155 of the GOT1000 series
•GT27,GT25 of the GOT2000 series
(4) Fit the CC-Link IE communication unit in the GOT case.
(5) Fix the CC-Link IE communication unit by tightening its mounting screws
(4 places) with a tightening torgue of 0.36 to 0.48 N•m.
4)
3)
Remove the connector cover.
Содержание GT15-J71GP23-SX