3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.4 GOT Side Settings
3.4 GOT Side Settings
3.4.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Azbil
• Controller Type: Set as follows.
<When connecting to DMC50 and AHC2001>
Azbil DMC50
<When connecting to a module other than above>
Azbil SDC/DMC
• I/F: Interface to be used
• Driver: Azbil SDC/DMC
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
3.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
3.4.2
Communication detail settings
*1
Do not specify "0".
*2
Format is ignored when connecting to DMC50.
*3
Host Address is ignored when connecting to DMC10 or SDC.
*4
Host Address is valid when connecting to DMC50.
Devices to be the target of Host Address setting differ
depending on the system configuration.
<When connecting to the temperature controller via COM
module>
Specify the station No. of the COM module.
<When connecting to the temperature controller directly>
Specify the station No. of the temperature controller.
2.
3.
4.
Click!
Item
Description
Range
Transmission
Speed
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
7bits/8bits
Stop Bit
Specify the stop bit length for
communications.
(Default: 1bit)
1bit/2bits
Parity
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
None
Even
Odd
Retry
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
0 to 5times
Timeout Time
Set the time period for a
communication to time out.
(Default: 3sec)
3 to 30sec
Host Address
*3*4
Specify the host address (station No.
of the GOT to which the temperature
controller is connected) in the
connected network.
(Default: 1)
1 to 15
Delay Time
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
*1
(Default: 1ms)
0 to 300ms
Format
*2
Select the communication format.
(Default: 1)
format 1: only continuous access
format 2: continuous and random
access
1/2
Содержание GOT 1000 Series
Страница 2: ......
Страница 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 78: ......
Страница 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Страница 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Страница 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Страница 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Страница 426: ...15 22 15 CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC 15 6 Device Range that Can Be Set ...
Страница 432: ...REVISIONS 3 ...
Страница 435: ......