3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.3 Connection Diagram
RS485 connection diagram 10) (For GT16)
*1
Terminating resistor should be provided for a temperature controller which will be a terminal.
*2
Set the terminating resistor of GOT as follows.
GT16, GT15, GT12: Set the terminating resistor setting switch of the GOT main unit to "100 OHM".
■
Connecting terminating resistors
*3
Connect FG grounding to the single-sided end of a cable shield line.
GOT side
*2
Temperature controller
side
terminal for RS-485 port1
Temperature controller
side
terminal for RS-485 port1
SDA1 (TXD1+)
SDB1 (TXD1-)
RDA1 (RXD1+)
RDB1 (RXD1-)
SG
SDA2 (TXD2+)
SDB2 (TXD2-)
RDA2 (RXD2+)
RDB2 (RXD2-)
RSA (RTS+)
RSB (RTS-)
CSA (CTS+)
CSB (CTS-)
NC
RDA1
RDB1
SDA1
SDB1
SG1
1
2
3
4
13
5
6
7
8
9
10
11
12
14
Shell
6
7
4
5
8
6
7
4
5
8
*3
*3
RDA1
RDB1
SDA1
SDB1
SG1
Terminating resistor (150Ω 1/2W)
*1
Содержание GOT 1000 Series
Страница 2: ......
Страница 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 78: ......
Страница 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Страница 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Страница 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Страница 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Страница 426: ...15 22 15 CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC 15 6 Device Range that Can Be Set ...
Страница 432: ...REVISIONS 3 ...
Страница 435: ......