A.4.4
Special Function Modules
햲
When analog special function blocks (FX
0N
-3A, FX
2N
-2AD and FX
2N
-2DA) are connected to an input/ output po-
wered extension unit (FX
2N
-32E
첸
or FX
2N
-48E
첸
), the following limitation must be taken into consideration.
(When the blocks are connected to the base unit, this limitation is not applied.)
The total current consumption of the analog special function blocks (FX
0N
-3A, FX
2N
-2AD and FX
2N-
2DA) should
be less than the following current values.
- When connected to FX
2N
-32E
첸
: 190 mA or less
- When connected to FX2N-48E
첸
: 300 mA or less.
햳
When the voltage of the external DC power supply is 5 V DC, the current is 100 mA.
햴
A FX
2N
-16CCL-M cannot be used together with a FX
2N
-32ASI-M. The following number of points is added accord-
ing to the products connected to the network: (Number of remote I/O stations) x 32 points.
햵
A FX
2N
-32ASI-M cannot be used together with a FX
2N
-16CCL-M. Only one unit can be added to the whole sys-
tem. The following number of points is added according to the products connected to the network:
(Number of active slaves) x 8 points.
NOTE
When applying a DC power type base unit, calculate the current consumption at startup.
Number of Occupied Input/Output Points and Current Consumption
Appendix
A - 16
MITSUBISHI ELECTRIC
Type
Number of
occupied
I/O points
Current consumption [mA]
5 V DC
24 V DC (internal) 24 V DC (external)
At start up
FX
3U
-2HC
8
245
0
0
—
FX
3U
-4AD
8
110
0
90
—
FX
3U
-4DA
8
120
0
160
—
FX
3U
-4LC
8
160
0
50
—
FX
3U
-20SSC-H
8
100
0
220
—
FX
2N
-2AD
8
20
50
���
0
170
FX
2N
-2DA
8
30
85
���
0
190
FX
2N
-4AD
8
30
0
55
—
FX
2N
-4DA
8
30
0
200
—
FX
2N
-4AD-TC
8
30
0
50
—
FX
2N
-4AD-PT
8
30
0
50
—
FX
2N
-8AD
8
50
0
80
—
FX
2N
-5A
8
70
0
90
—
FX
2N
-2LC
8
70
0
55
—
FX
2N
-1HC
8
90
0
0
—
FX
2N
-1PG-E
8
55
0
40
—
FX
2N
-10PG
8
120
0
70
햳
—
FX
2N
-232IF
8
40
0
80
—
FX
2N
-16CCL-M
8
햴
0
0
150
—
FX
2N
-32CCL-M
8
130
0
50
—
FX
2N
-32ASI-M
8
햵
150
0
70
—
FX
0N
-3A
8
30
90
���
0
165
FX
2N
-10GM
8
—
—
5
—
FX
2N
-20GM
8
—
—
10
—
Содержание FX2N-32CAN
Страница 1: ...MITSUBISHI ELECTRIC FACTORY AUTOMATION Programmable Logic Controllers GX IEC Developer ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...IV MITSUBISHI ELECTRIC ...
Страница 18: ...Modular PLC Training Hardware Course Overview and Requirements 1 2 MITSUBISHI ELECTRIC ...
Страница 172: ...Monitoring Instances of Function Blocks Advanced Monitoring Functions 7 12 MITSUBISHI ELECTRIC ...
Страница 176: ...Device Edit 8 4 MITSUBISHI ELECTRIC ...
Страница 190: ...Assigning DUT Variables to Function Blocks Data Unit Types DUT 10 10 MITSUBISHI ELECTRIC ...
Страница 198: ...Array Example Single Dimension Array Arrays 11 8 MITSUBISHI ELECTRIC ...
Страница 219: ...Sequential Function Chart SFC SFC Elements Training Manual GX IEC Developer 14 3 ...
Страница 220: ...14 3 SFC configuration examples SFC configuration examples Sequential Function Chart SFC 14 4 MITSUBISHI ELECTRIC ...
Страница 230: ...Structured Text Program Example IEC Structured Text 16 4 MITSUBISHI ELECTRIC ...
Страница 248: ...Configuring GX IEC Developer to access the PLC on Ethernet Ethernet Communications 18 10 MITSUBISHI ELECTRIC ...
Страница 278: ...PLC Components Glossary Appendix A 18 MITSUBISHI ELECTRIC ...
Страница 283: ......