THERMISTOR INTERFACE

5.3 Parameter setting

The following parameters are provided for use of the thermistor interface.

5.4 Motor thermal relay alarm

(1) When Pr. 407 = "0 to 100"

Normally, set 30s in Pr. 407. If the response level to a motor temperature is low, make adjustment to 
decrease the setting.

Detection of a 145°C (293°F) or higher motor temperature continuously for 10s results in a motor thermal 
relay alarm (E.THM), shutting off the output.

Detection of a -30°C (-22°F) or lower motor temperature during operation results in a motor thermal 
relay alarm (E.THM), shutting off the output.
During a stop, a motor thermal relay alarm (E.THM) does not occur.

The OH terminal (thermal relay protector input) is invalid.

(2) When Pr. 407 = "9999"

A  motor thermal relay alarm (E.THM) is not detected by the FR-V5AX.

Parameter

Name

Factory 

setting

Setting 

range

Minimum 

input 

increments

Remarks

407

Motor temperature detection filter

9999

0 to 100s, 9999

1s

9999: No function

925

Motor temperature detection calibration

100%

0 to 200%

0.1%

CAUTION

The vector inverter motor with thermistor does not have a thermal relay protector. When using this 
type of motor, always set a value other than "9999" in Pr. 407 "motor temperature detection filter". 
If the setting remains "9999", motor protection cannot be provided.

Содержание FR-V5AX

Страница 1: ......

Страница 2: ...Thank you for choosing the Mitsubishi vector inverter option unit ...

Страница 3: ......

Страница 4: ... 3 Usage ...

Страница 5: ...CONTENTS ...

Страница 6: ...1 PRE OPERATION INSTRUCTIONS ...

Страница 7: ...2 INSTALLATION ...

Страница 8: ...INSTALLATION ...

Страница 9: ...INSTALLATION ...

Страница 10: ...3 HIGH RESOLUTION ANALOG INPUT ...

Страница 11: ...HIGH RESOLUTION ANALOG INPUT ...

Страница 12: ...HIGH RESOLUTION ANALOG INPUT ...

Страница 13: ...HIGH RESOLUTION ANALOG INPUT ...

Страница 14: ...HIGH RESOLUTION ANALOG INPUT ...

Страница 15: ...4 EXTRA CONTACT INPUT FUNCTION ...

Страница 16: ...EXTRA CONTACT INPUT FUNCTION ...

Страница 17: ...EXTRA CONTACT INPUT FUNCTION ...

Страница 18: ...5 THERMISTOR INTERFACE ...

Страница 19: ...THERMISTOR INTERFACE ...

Страница 20: ...THERMISTOR INTERFACE ...

Страница 21: ...THERMISTOR INTERFACE ...

Страница 22: ...THERMISTOR INTERFACE ...

Страница 23: ......

Отзывы: