THERMISTOR INTERFACE
5.3 Parameter setting
The following parameters are provided for use of the thermistor interface.
5.4 Motor thermal relay alarm
(1) When Pr. 407 = "0 to 100"
Normally, set 30s in Pr. 407. If the response level to a motor temperature is low, make adjustment to
decrease the setting.
•
Detection of a 145°C (293°F) or higher motor temperature continuously for 10s results in a motor thermal
relay alarm (E.THM), shutting off the output.
•
Detection of a -30°C (-22°F) or lower motor temperature during operation results in a motor thermal
relay alarm (E.THM), shutting off the output.
During a stop, a motor thermal relay alarm (E.THM) does not occur.
•
The OH terminal (thermal relay protector input) is invalid.
(2) When Pr. 407 = "9999"
A motor thermal relay alarm (E.THM) is not detected by the FR-V5AX.
Parameter
Name
Factory
setting
Setting
range
Minimum
input
increments
Remarks
407
Motor temperature detection filter
9999
0 to 100s, 9999
1s
9999: No function
925
Motor temperature detection calibration
100%
0 to 200%
0.1%
CAUTION
The vector inverter motor with thermistor does not have a thermal relay protector. When using this
type of motor, always set a value other than "9999" in Pr. 407 "motor temperature detection filter".
If the setting remains "9999", motor protection cannot be provided.
Содержание FR-V5AX
Страница 1: ......
Страница 2: ...Thank you for choosing the Mitsubishi vector inverter option unit ...
Страница 3: ......
Страница 4: ... 3 Usage ...
Страница 5: ...CONTENTS ...
Страница 6: ...1 PRE OPERATION INSTRUCTIONS ...
Страница 7: ...2 INSTALLATION ...
Страница 8: ...INSTALLATION ...
Страница 9: ...INSTALLATION ...
Страница 10: ...3 HIGH RESOLUTION ANALOG INPUT ...
Страница 11: ...HIGH RESOLUTION ANALOG INPUT ...
Страница 12: ...HIGH RESOLUTION ANALOG INPUT ...
Страница 13: ...HIGH RESOLUTION ANALOG INPUT ...
Страница 14: ...HIGH RESOLUTION ANALOG INPUT ...
Страница 15: ...4 EXTRA CONTACT INPUT FUNCTION ...
Страница 16: ...EXTRA CONTACT INPUT FUNCTION ...
Страница 17: ...EXTRA CONTACT INPUT FUNCTION ...
Страница 18: ...5 THERMISTOR INTERFACE ...
Страница 19: ...THERMISTOR INTERFACE ...
Страница 20: ...THERMISTOR INTERFACE ...
Страница 21: ...THERMISTOR INTERFACE ...
Страница 22: ...THERMISTOR INTERFACE ...
Страница 23: ......