(H) Protective function parameter
Parameters
5 - 176
5.7.9
Limiting the output frequency (maximum/minimum frequency)
Motor speed can be limited. Clamp the output frequency at the upper and lower limits.
For the FR-F820-02330(55K)or lower and FR-F840-01160(55K) or lower.
For the FR-F820-03160(75K)or higher and FR-F840-01800(75K) or higher.
Setting the maximum frequency (Pr. 1, Pr. 18)
●
Set Pr. 1 "Maximum frequency" to the upper limit of the output frequency. If the value of the
frequency command entered is higher than the setting, the output frequency is clamped at the
maximum frequency.
●
To operate at a frequency higher than the 120 Hz, adjust the upper output frequency limit with
Pr. 18 "High speed maximum frequency". (When setting a frequency in Pr. 18, the Pr. 1 setting
automatically changes to the frequency set in Pr. 18. Also, when setting a frequency in Pr. 1, the
Pr. 18 setting automatically changes to the frequency set in Pr. 1.)
Setting the minimum frequency (Pr. 2)
●
Set Pr. 2 "Minimum frequency" to the lower limit of the output frequency.
●
If the set frequency is Pr. 2 or less, the output frequency is clamped at Pr. 2 (will not fall below Pr. 2).
E
CAUTION:
When the emergency drive operation is performed, the operation is continued or the retry is
repeated even when a fault occurs, which may damage or burn the inverter and motor. Before
restarting the normal operation after using this function, make sure that the inverter and motor
have no fault. Any damage of the inverter or the motor caused by using the emergency drive
function is not covered by the warranty even within the guarantee period.
Pr.
Name
Initial
value
Setting
range
Description
1
H400
Maximum frequency
0 to 120 Hz Set the upper limit of the output frequency.
2
H401
Minimum frequency
0 Hz
0 to 120 Hz Set the lower limit of the output frequency.
18
H402
High speed maximum
frequency
0 to 590 Hz Set when operating at 120 Hz or higher.
Fig. 5-61:
Maximum and minimum output frequency
I002590E
0
Output frequency
(Hz)
Clamped at the
maximum frequency
Frequency setting
Clamped at the
minimum frequency
Pr. 1
Pr. 18
Pr. 2
(4
5, 10 V
(20 mA)
(4 mA)
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......