(M) Monitor display and monitor output signal
Parameters
5 - 208
Differs according to capacities. (FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower/
FR-F820-03160(75K) or higher, FR-F840-01800(75K) or higher)
When the output current is less than the specified current level (5% of the rated inverter current),
the output current is monitored as 0 A. Therefore, the monitored value of an output current and
output power may be displayed as "0" when using a much smaller-capacity motor compared to
the inverter or in other instances that cause the output current to fall below the specified value.
Setting of Pr. 1018 "Monitor with sign selection" is required.
The setting is available only with terminal AM (Pr. 158).
"
The setting is available only with terminal FM/CA (Pr. 54).
PID set point
0.1%
52
100%
Refer to page 5-362 for the
PID control.
PID measured value
0.1%
53
100%
PID deviation
0.1%
100%
Motor thermal load
factor
0.1%
61
Motor thermal
operation level
(100%)
Inverter thermal load
factor
0.1%
62
Inverter thermal
operation level
(100%)
PID measured value 2
0.1%
67
100%
Refer to page 5-362 for the
PID control.
PID input pressure value
0.1%
69
100%
Displays the input pressure
value of the PID input
pressure control function.
PLC function analog
output
0.1%
70
100%
Refer to page 5-433 for the
PLC function.
BACnet terminal FM/CA
output level
0.1%
100%
The value set in the Analog
Output object
(ID = 0: Terminal FM/CA) for
BACnet communication is
output.
BACnet terminal AM
output level
0.1%
100%
The value set in the Analog
Output object
(ID = 1: Terminal AM) for
BACnet communication is
output. (The output is
always negative regardless
of the Pr.290 setting when
the monitored value is
negative.)
Remote output value 1
0.1%
87
1000%
Refer to page 5-243 for the
analog remote output.
Remote output value 2
0.1%
88
1000%
Remote output value 3
0.1%
89
1000%
Remote output value 4
0.1%
90
1000%
PID manipulated
variable
0.1%
100%
Output with a minus sign
(terminal AM)
Second PID set point
0.1%
92
100%
Refer to page 5-362 for the
PID control.
Second PID measured
value
0.1%
93
100%
Second PID deviation
0.1%
200%
Second PID measured
value 2
0.1%
95
100%
Second PID manipulated
variable
0.1%
100%
Control circuit
temperature
1 °C
98
100 °C
Terminal FM/CA: 0 to 100°C
Terminal AM: -20 to 100°C
Types of monitor
Unit
Pr. 54
(FM/CA)
Pr. 158 (AM)
setting
Terminal
FM, CA, AM
Full-scale value
Negative
(-) output
Remarks
Tab. 5-96:
Monitor description list (2)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......