Communication operation and setting
4
(6) Modbus registers
z
System environment variable
*1
The communication parameter values are not cleared.
*2
For write, set the data as a control input instruction. For read, data is read as an inverter operating status.
*3
For write, set data as the operation mode setting. For read, data is read as the operation mode status.
z
Real-time monitor
Refer to
page 131
for details of the monitor description.
*1
Input terminal monitor details
*2
Output terminal monitor details
Register
Definition
Read/Write
Remarks
40002
Inverter reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
*1
Write
Set H5A96 as a written value.
40007
All parameter clear
*1
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
*2
Read/write
See below.
40010
Operation mode/inverter setting
*3
Read/write
See below.
40014
Running frequency (RAM value)
Read/write
According to the
Pr. 37
and
Pr. 144
settings, the
frequency and selectable speed are in 1r/min
increments.
40015
Running frequency (EEPROM value)
Write
b15
b0
⎯
⎯
⎯
⎯
CS
RES
STOP
MRS
JOG
RH
RM
RL
RT
AU
STR
STF
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
ABC2 ABC1
FU
OL
IPF
SU
RUN
*3
The setting depends on capacities. (55K or less/75K or more)
*4
When
Pr.37
= "1 to 9998" or
Pr. 144
= "2 to 10, 102 to 110," the unit is an integral value (one increment).
(Refer to page 130
<Inverter status/control input instruction>
*1
The signal within parentheses is the initial setting. The description changes depending on the setting of
Pr. 180 to Pr. 189 (input
terminal function selection) (page115)
.
Each assigned signal is valid or invalid depending on NET.
(Refer to page 186)
*2
The signal within parentheses is the initial setting. The description changes depending on the setting of
Pr. 190 to Pr. 196 (output
terminal function selection) (page121)
.
Bit
Definition
Control input instruction
Inverter status
0
Stop command
RUN (inverter running)
*2
1
Forward rotation command
Forward rotation
2
Reverse rotation command
Reverse rotation
3
RH (high speed operation command)
*1
SU (up to frequency)
*2
4
RM (middle speed operation command)
*1
OL (overload)
*2
5
RL (low speed operation command)
*1
IPF (instantaneous power failure)
*2
6
JOG (Jog operation)
*1
FU (frequency detection)
*2
7
RT (second function selection)
*1
ABC1 (fault)
*2
8
AU (current input selection)
*1
ABC2 (
⎯
)
*2
9
CS
(selection of automatic restart after
instantaneous power failure)
*1
0
10
MRS (output stop)
*1
0
11
STOP (start self-holding)
*1
0
12
RES (reset)
*1
0
13
0
0
14
0
0
15
0
Fault occurrence
<Operation mode/inverter setting>
The restrictions depending on the
operation mode changes according
to the computer link specifications.
Mode
Read
Value
Written
Value
EXT
H0000
H0010
PU
H0001
⎯
EXT
JOG
H0002
⎯
PU
JOG
H0003
⎯
NET
H0004
H0014
PU+
EXT
H0005
⎯
Register
Description
Increments
40201 Output frequency/Speed
0.01Hz/1
40202 Output current
0.01A/0.1A
40203 Output voltage
0.1V
40205
Frequency setting value/Speed
setting
0.01Hz/1
40206 Running speed
1r/min
40208 Converter output voltage
0.1V
40209 Regenerative brake duty
0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211
Output current peak value
0.01A/0.1A
40212 Converter output voltage peak value
0.1V
40213 Input power
0.01kW/
0.1kW
40214 Output power
0.01kW/
0.1kW
⎯
40216 Output terminal status
⎯
40217 Load meter
0.1%
40220 Cumulative energization time
1h
40223 Actual operation time
1h
40224 Motor load factor
0.1%
40225 Cumulative power
1kWh
40250 Power saving effect
Variable
40251 Cumulative saving power
Variable
40252 PID set point
0.1%
40253 PID measured value
0.1%
40254 PID deviation
0.1%
Register
Description
Increments