![Mitsubishi Electric FR-F700PJ Series Скачать руководство пользователя страница 326](http://html.mh-extra.com/html/mitsubishi-electric/fr-f700pj-series/fr-f700pj-series_instruction-manual_239805326.webp)
321
Inspection items
6.1.7
Replacement of parts
The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced
performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
Use the life check function as a guidance of parts replacement.
Estimated lifespan for when the yearly average surrounding air temperature is 40°C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Output current: 80% of the rated inverter current
(1) Cooling fan
The replacement interval of the cooling fan used for cooling the parts generating heat such as the main circuit semiconductor
is greatly affected by the surrounding air temperature. When unusual noise and/or vibration is noticed during inspection, the
cooling fan must be replaced immediately.
Part Name
Estimated lifespan
Description
Cooling fan
10 years
Replace (as required)
Main circuit smoothing
capacitor
10 years
Replace (as required)
On-board smoothing
capacitor
10 years
Replace the board (as required)
Relays
—
as required
NOTE
For parts replacement, contact the nearest Mitsubishi FA Center.
Removal
1) Push the hooks from above and remove the fan cover.
3.7K or lower
5.5K or higher
2) Disconnect the fan connectors.
3) Remove the fan.
3.7K or lower
Example for FR-F740PJ-1.5K
5.5K or higher
Example for FR-F740PJ-7.5K
Fan connector
Fan
Fan cover
Fan
Fan cover
Fan connector
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...