251
Special operation and frequency control
C42
(934)
PID display bias
coefficient
9999
0 to
500.00
Set the coefficient on bias (minimum) side of terminal 4 input.
9999
Displayed in %.
C43
(934)
PID display bias
analog value
20%
0 to
300.0%
Set the converted % on bias (minimum) side current /voltage of terminal
4 input.
C44
(935)
PID display gain
coefficient
9999
0 to
500.00
Set the coefficient on gain (maximum) side of the terminal 4 input.
9999
Displayed in %.
C45
(935)
PID display gain
analog value
100%
0 to
300.0%
Set the converted % on gain (maximum) side of current/voltage of
terminal 4 input.
The above parameters can be set when
Pr. 160 Extended function display selection
="0".
Pr. 129, Pr. 130, Pr. 133 and Pr. 134
can be set during operation. These can also be set independently of the operation mode.
If
C42(Pr.934)
and
C44(Pr.935)
are both set to values other than "9999," the setting range for
Pr. 131
to
Pr. 133
and
Pr. 553
become only "9999," and % is not
displayed in the setting range of
Pr. 577
. (Values set in
Pr. 553
and
Pr. 577
are converted as differentials. )
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
Parameter
Number
Name
Initial
Value
Setting
Range
Description