Simple mode parameter list
4 ADJUSTMENT
4.1 Simple mode parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made from
the operation panel (FR-DU07). For details of parameters, refer to
Instruction Manual (applied)
.
POINT
Only simple mode parameters are displayed by the initial setting of
Pr. 160 User group read selection
. Set
Pr. 160 User
group read selection
as required. (
Refer to page 106
Pr. 160
Description
9999
(Initial Value)
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be displayed.
1
Only the parameters registered in the user group can be displayed.
Parameter
Number
Name
Incre
ments
Initial
Value
Range
Applications
Refer
to
0
Torque boost
0.1%
6/4/3/2/
1.5/1%
0 to 30%
Set to increase a starting torque or when the
motor with a load will not rotate, resulting in an
alarm [OL] and a trip [OC1]
*1
Initial values differ according to the inverter
capacity. (00023 / 00038 to 00083 / 00126,00170
/ 00250 to 00770 / 00930, 01160 /01800 or more)
1
Maximum
frequency
0.01Hz
120/
60Hz
0 to 120Hz
Set when the maximum output frequency need
to be limited.
*2
Initial values differ according to the inverter
capacity. (01160 or less/01800 or more)
2
Minimum
frequency
0.01Hz
0Hz
0 to 120Hz
Set when the minimum output frequency need
to be limited.
3
Base frequency
0.01Hz
50Hz
0 to 400Hz
Check the motor rating plate.
4
Multi-speed setting
(high speed)
0.01Hz
50Hz
0 to 400Hz
Set when changing the preset speed in the
parameter with a terminal.
5
Multi-speed setting
(middle speed)
0.01Hz
30Hz
0 to 400Hz
6
Multi-speed setting
(low speed)
0.01Hz
10Hz
0 to 400Hz
7
Acceleration time
0.1s
5/15s
0 to 3600s
Acceleration/deceleration time can be set.
*3
Initial values differ according to the inverter
capacity. (00170 or less/00250 or more)
8
Deceleration time
0.1s
10/30s
0 to 3600s
9
Electronic thermal
O/L relay
0.01/
0.1A
Rated
inverter
output
current
0 to 500/
0 to 3600A
Protect the motor from overheat by the inverter.
Set the rated motor current.
*4
Setting increments and setting range differ
according to the inverter capacity.
(01160 or less/01800 or more)
60
Energy saving
control selection
1
0
0, 4, 9
The inverter output voltage is minimized when
using for fan and pump applications.
79
Operation mode
selection
1
0
0, 1, 2, 3, 4, 6, 7
Select the start command location and frequency
command location.
125
Terminal 2
frequency setting
gain frequency
0.01Hz
50Hz
0 to 400Hz
Frequency for the maximum value of the
potentiometer (at 5V) can be changed.
126
Terminal 4
frequency setting
gain frequency
0.01Hz
50Hz
0 to 400Hz
Frequency at 20mA input can be changed.
160
User group read
selection
1
9999
0, 1, 9999
Make extended parameters valid
—