12. (M) Item and Output Signal for Monitoring
12.3 Monitor display selection for terminals FM and AM
*1
The inverter regards the output current which is less than the specified current level (5% of the rated inverter current) as 0 A. Therefore, each
readout of an output current and output power may show "0" if a too small-capacity motor is used as contrasted with the inverter capacity and the
output current falls below the specified value.
*2
The setting is available only in
Pr.158
(terminal AM).
Frequency monitor reference (Pr.55)
• Enter the full scale value of a meter used to monitor the output frequency, frequency setting value, or dancer main speed
setting via terminal FM or terminal AM.
• For the FM type inverter, enter the full-scale value of the meter corresponding to a pulse train of 1440 pulses/s output via
terminal FM. Enter the frequency value (for example, 60 Hz or 120 Hz) at full scale of the meter (1 mA analog meter)
installed between terminal FM and terminal SD. Pulse speed is proportional to the output frequency of the inverter. (The
maximum pulse train output is 2400 pulses/s.)
Electronic thermal O/L
relay load factor
0.1%
10
Electronic thermal O/
L relay (100%)
Output current peak
value
0.01 A
11
Pr.56
Converter output voltage
peak value
0.1 V
12
200 V class: 400 V,
400 V class: 800 V,
575 V class: 1000 V
Input power
0.01 kW
13
Inverter rated power ×
2
Output power
0.01 kW
14
Inverter rated power ×
2
Load meter
0.1%
17
Pr.866
Motor excitation current
0.01 A
18
Pr.56
Reference voltage output —
21
—
Terminal FM: 1440 pulse/s is
output.
Terminal AM: Output is 10 V.
Motor load factor
0.1%
24
200%
Torque command
0.1%
32
Pr.866
○
Torque current command 0.1%
33
Pr.866
○
Energy saving effect
Increment and unit
vary depending on
the parameter
settings.
50
Inverter capacity
For the information of the power
saving effect monitoring, refer to
PID set point
0.1%
52
100%
Refer to
for the PID
control.
PID measured value
0.1%
53
100%
PID deviation
0.1%
54
100%
○
Motor thermal load factor 0.1%
61
Motor thermal
activation level
(100%)
Inverter thermal load
factor
0.1%
62
Inverter thermal
activation level
(100%)
PID measured value 2
0.1%
67
100%
Refer to
for the PID
control.
PLC function analog
output
0.1%
70
100%
○
Enabled when
Pr.414
≠
"0".
Refer to
for the PLC
function.
PID manipulated amount 0.1%
91
100%
○
Refer to
for the PID
control.
Dancer main speed
setting
0.01 Hz.
97
Pr.55
For details on dancer control, refer
to
Monitor item
Increment and
unit
Pr.54 (FM),
Pr.158 (AM)
setting
Terminal FM/AM
full-scale value
Negative
output
Remarks
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...