12. (M) Item and Output Signal for Monitoring
12.2 Monitor item selection on operation panel or via communication
*1
Power is measured in the range of 0 to 99999.99 kWh, and displayed in 4 digits. After the watt-hour meter (cumulative power counter) reaches
"99.99" (999.99 kWh), the meter displays values in 0.1 increments such as "100.0" (1000.0 kWh). Use
Pr.891
to shift the decimal point position
when the monitored value becomes equal to or higher than 10000 kWh.
• The decimal point position on the watt-hour meter can be shifted to left. The number of digits to be shifted is equal to the
setting of
Pr.891 Cumulative power monitor digit shifted times
. For example, when
Pr.891
= "2", the cumulative power
value 1278.56 kWh is displayed as 12.78 (in 100 kWh increments) on the operation panel, or displayed as 12 on a display
used for monitoring via communication.
• When
Pr.891
= "0 to 4", the meter stops at the maximum number. When
Pr.891
= "9999", the meter returns to 0 and the
counting starts again.
• The cumulative power can be monitored as 32-bit data via communication by setting
Pr.52
= "77 to 80". The maximum
monitored value is 42949672 kWh in 1 kWh increments or 42949672.94 kWh in 0.01 kWh increments.
Pr.891
setting is
invalid while 32-bit cumulative power is monitored. (For details on communication for 32-bit cumulative power monitor, refer
to the Instruction Manual (Communication) or the Instruction Manual of the communication option.)
• Writing "0" in
Pr.170
clears the cumulative power monitor.
NOTE
• When
Pr.170
is read just after "0" has been written in
Pr.170
, the setting "9999" or "10" is displayed.
Monitoring cumulative energization time (Pr.563)
• When the cumulative energization time is selected as a monitor item (
Pr.52
= "20"), the counter of cumulative energization
time since the inverter shipment accumulated every hour is displayed.
• One hour is displayed as "0.001", and the value is counted up to "65.53".
• The EEPROM is updated every minute until the cumulative energization time reaches one hour, and then the EEPROM is
updated every 10 minutes. The EEPROM is also updated at power OFF.
• When the cumulative energization time counter reaches 65535, it starts from 0 again. The number of times the cumulative
energization time counter reaches 65535 can be checked with
Pr.563
.
NOTE
• The cumulative energization time does not increase if the power is turned OFF after less than an hour.
Actual operation time monitoring (Pr.171, Pr.564)
• On the actual operation time monitoring (
Pr.52
= "23"), the inverter running time is added up every hour. (Time is not added
up during a stop.)
• One hour is displayed as "0.001", and the value is counted up to "65.53".
• The values are stored in EEPROM every 10 minutes. The EEPROM is also updated at power OFF.
• When the cumulative energization time counter reaches 65535, it starts from 0 again. The number of times the actual
operation time counter reaches 65535 can be checked with
Pr.564
.
• Setting "0" in
Pr.171
clears the actual operation time meter.
NOTE
• The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
• Once "0" is set in
Pr.171
, the setting of
Pr.171
is always turned to "9999" afterwards. Setting "9999" does not clear the actual
operation time meter.
Hiding the decimal places for the monitors (Pr.268)
• The numerical figures after a decimal point displayed on the operation panel may fluctuate during analog input, etc. The
decimal places can be hidden by selecting the decimal digits with
Pr.268
.
Pr.268 setting
Description
9999 (initial value) No function
0
For the first or second decimal places (0.1 increments or 0.01 increments) of the monitor, numbers
in the first decimal place and smaller are rounded to display an integral value (1 increments). The
monitor value equal to or smaller than 0.99 is displayed as 0.
1
When monitoring with the second decimal place (0.01 increments), the 0.01 decimal place is
dropped and the monitor displays the first decimal place (0.1 increments). When monitoring with the
first decimal place, the display will not change.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...