11. (H) Protective Function Parameters
11.11 Load characteristics fault detection
11.11
Load characteristics fault detection
This function is used to monitor whether the load is operating in normal condition by storing the speed/torque relationship in
the inverter to detect mechanical faults or for maintenance. When the load operating condition deviates from the normal range,
the protective function is activated or the warning is output to protect the inverter or the motor.
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
).
Load characteristics reference setting (Pr.1481 to Pr.1487)
• Use
Pr.1481 to Pr.1485
to set the reference value of load characteristics.
Pr.
Name
Initial value
Setting
range
Description
Gr.1
Gr.2
1480
H520
Load characteristics
measurement mode
0
0
Load characteristics measurement mode does not start.
(Measurement of load characteristics complete without fault.)
1
Load characteristics measurement mode is started.
2, 3, 4, 5,
81, 82, 83,
84, 85
The load characteristics measurement status is displayed.
(Read-only)
1481
H521
Load characteristics load
reference 1
9999
0% to 400%
Used to set the reference value of normal load characteristics.
8888: The present load status is written as reference status.
9999: The load reference is invalid.
1482
H522
Load characteristics load
reference 2
9999
1483
H523
Load characteristics load
reference 3
9999
1484
H524
Load characteristics load
reference 4
9999
1485
H525
Load characteristics load
reference 5
9999
1486
H526
Load characteristics
maximum frequency
60 Hz
50 Hz
0 to 590 Hz
Used to set the upper frequency limit of the load characteristics
fault detection range.
1487
H527
Load characteristics
minimum frequency
6 Hz
0 to 590 Hz
Used to set the lower frequency limit of the load characteristics
fault detection range.
1488
H531
Upper limit warning detection
width
20%
0% to 400%
Used to set the detection range of when the upper limit load fault
warning is output.
9999
Function disabled
1489
H532
Lower limit warning detection
width
20%
0% to 400%
Used to set the detection range of when the lower limit load fault
warning is output.
9999
Function disabled
1490
H533
Upper limit fault detection
width
9999
0% to 400%
Used to set the detection range of when output is shut-off when
the upper limit load fault occurs.
9999
Function disabled
1491
H534
Lower limit fault detection
width
9999
0% to 400%
Used to set the detection range of when output is shut-off when
the lower limit load fault occurs.
9999
Function disabled
1492
H535
Load status detection signal
delay time / load reference
measurement waiting time
1 s
0 to 60 s
Used to set the waiting time after the load fault is detected until
warning output or output shutoff.
In the load characteristics measurement mode, set the waiting
time after the load measurement frequency is reached until the
load reference is set.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...