8. (E) Environment Setting Parameters
8.15 PWM carrier frequency and Soft-PWM control
8.15
PWM carrier frequency and Soft-PWM control
The motor sound can be changed.
Changing the PWM carrier frequency (Pr.72)
• The PWM carrier frequency of the inverter can be changed.
• Changing the PWM carrier frequency can be effective for avoiding the resonance frequency of the mechanical system or
motor, as a countermeasure against EMI generated from the inverter, or for reducing leakage current caused by PWM
switching.
• Under Real sensorless vector control, Vector control, and PM sensorless vector control, the following carrier frequencies
are used.
*1
The carrier frequency is automatically changed to 2 kHz in the low-speed range (lower than 3 Hz) under Real sensorless vector control, or in the
low-speed range (lower than 10% of the rated motor frequency) under PM sensorless vector control.
NOTE
• The carrier frequency may be automatically lowered in the low-speed range (lower than about 10 Hz) for the ND rating, and
over the entire speed range for the LD rating.
Motor noise increases, but not to the point of failure.
Soft-PWM control (Pr.240)
• Soft-PWM control is a function that changes the motor noise from a metallic sound into an inoffensive, complex tone.
• Setting
Pr.240
= "1" will enable the Soft-PWM control.
• To enable the Soft-PWM control, set
Pr.72
to 5 kHz or less.
PWM carrier frequency automatic reduction function (Pr.260)
• Setting
Pr.260
= "10" (initial value) will enable the PWM carrier frequency auto-reduction function. If a heavy load is
continuously applied while the inverter carrier frequency is set to 3 kHz or higher (
Pr.72
≥
"3"), the carrier frequency is
automatically reduced to prevent occurrence of the inverter overload trip (electronic thermal O/L relay function) (E.THT).
Motor noise increases, but not to the point of failure.
• When the carrier frequency automatic reduction function is used, operation with the carrier frequency set to 3 kHz or higher
(
Pr.72
≥
3) automatically reduces the carrier frequency for heavy-load operation as shown below.
Pr.
Name
Initial
value
Setting range
Description
72
E600
PWM frequency selection
1
0 to 15
The PWM carrier frequency can be changed. The setting value
represents the frequency in kHz. Note that "0" indicates 0.7 kHz,
"15" indicates 14.5 kHz.
240
E601
Soft-PWM operation
selection
1
0
Soft-PWM control disabled.
1
Soft-PWM control enabled.
260
E602
PWM frequency automatic
switchover
10
0
PWM carrier frequency automatic reduction function disabled
10
PWM carrier frequency automatic reduction function enabled
Pr.72 setting
Carrier frequency (kHz)
0 to 5
2
6 to 9
10 to 13
10
14, 15
14
Pr.260 setting
Pr.570 setting
Carrier frequency automatic reduction operation
10
1 (LD)
The carrier frequency will reduce automatically with continuous operation of 85% of the
inverter rated current or higher.
2 (ND)
The carrier frequency will reduce automatically with operation of 170% of the inverter ND
rated current or higher (only in a low-speed range).
0
1 (LD)
Without carrier frequency automatic reduction (Perform continuous operation with the
carrier frequency set to 2 kHz or lower or with less than 85% of the inverter rated current
for the ND rating.)
2 (ND)
Without carrier frequency automatic reduction
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...