Causes and corrective actions
Troubleshooting
7 - 14
햲
This fault is only available for the frequency inverter FR-E700 SC EC.
Operation panel
indication
E.OPT
FR-PU04
FR-PU07
Option Fault
Name
Option fault
Description
Appears when a communication option is connected while Pr. 296 = "0 or 100."
Check point
Check if password lock is activated by setting Pr. 296 = "0, 100"
Corrective action
앫
To apply the password lock when installing a communication option, set Pr. 296 not equal to
"0,100".
앫
If the problem still persists after taking the above measure, please contact your sales
representative.
Operation panel
indication
E.OP1
FR-PU04
FR-PU07
Option slot alarm 1
Name
Communication option fault
Description
Stops the inverter output when a communication line fault occurs in the communication option.
Check point
앫
Check for a wrong option function setting and operation.
앫
Check that the plug-in option unit is plugged into the connector securely.
앫
Check for a break in the communication cable.
앫
Check that the terminating resistor is fitted properly.
Corrective action
앫
Check the option function setting, etc.
앫
Connect the plug-in option securely.
앫
Check the connection of communication cable.
앫
Connect the terminating resistor correctly.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......