Parameter
CC-Link IE Field Network Basic
FR-E700 SC EC/ENE
6 - 353
●
When Pr. 544 = "12" (compatible with the double setting of CC-Link Ver.2)
– Remote I/O (32 points)
Same as when Pr. 544 = 0 (Refer to page 6-351.)
– Remote register
햲
When Pr. 37 is not equal to "0", this will be machine speed display (1 increments).
햳
"n" indicates a value determined according to the station number setting.
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
RWwn
Monitor code 2
Monitor code 1
RWwn+1
Set frequency (0.01 Hz increments)
RWwn+2
Link parameter
extended setting
Instruction code
RWwn+3
Write data
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
Tab. 6-150:
Remote write register
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
RWrn
First monitor value
RWrn+1
Second monitor value
RWrn+2
Reply code 2
Reply code 1
RWrn+3
Read data
RWrn+4
Third monitor value
RWrn+5
Fourth monitor value
RWrn+6
Fifth monitor value
RWrn+7
Sixth monitor value
Tab. 6-151:
Remote read register