Monitor display and monitor output signals
Parameter
6 - 148
6.11.3
Reference of the terminal AM (analog voltage output) (Pr. 55, Pr. 56)
Analog voltage output from the terminal AM is available. Set the reference of the signal output from
terminal AM.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
햲
The above parameter allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Frequency monitoring reference (Pr. 55)
Set the full scale value when outputting the frequency monitor from terminal AM. Set the frequency
to be referenced when the frequency monitor (output frequency/set frequency) is selected for the
terminal AM display.
●
Set the frequency (output frequency/set frequency) when the voltage output at terminal AM is
10 V DC. The analog voltage output and frequency at terminal AM are proportional. (The maxi-
mum output voltage is 10 V DC.).
Pr. No. Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
55
Frequency monitoring
reference
햲
50 Hz
0–400 Hz
Full-scale value to output the output
frequency monitor value to terminal AM.
158 AM terminal function
selection
56
Current monitoring
reference
햲
Rated inverter
current
0–500 A
Full-scale value to output the output current
monitor value to terminal AM.
Fig. 6-73:
Frequency monitoring reference
I001164E
10 V DC
Setting range of Pr. 55
Initial value
Te
rminal AM
output v
oltage
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......