Simple mode parameter list
Basic settings
5 - 12
5.1.7
Large starting torque and low speed torque are necessary
(Advanced magnetic flux control, General-purpose magnetic flux vector
control) (Pr. 71, Pr. 80, Pr. 81, Pr. 800)
Advanced magnetic flux vector control can be selected by setting the capacity, poles and type of the
motor used in Pr. 80 and Pr. 81.
Advanced magnetic flux vector control or general-purpose magnetic flux vector control?
The low speed torque can be improved by providing voltage compensation so that the motor current
which meets the load torque to flow. Output frequency compensation (slip compensation) is made so
that the motor actual speed approximates a speed command value. Effective when load fluctuates
drastically, etc.
General-purpose magnetic flux vector control is the same function as it is for the FR-E500 series. Select
this control when operation characteristics as similar as possible are required when replacing from
the FR-E500 series. For other cases, select advanced magnetic flux vector control.
햲
Refer to appendix A for the rated inverter output current.
햳
Set a value other than "9999" in Pr. 80 and Pr. 81.
Pr. No. Name
Initial
Value
Setting Range
Description
9
Electronic thermal
O/L relay
Rated inverter
current
햲
0–500 A
Set the rated motor current.
71
Applied motor
0
0/1/3–6/13–16/23/24/40/43/44/
50/53/54
By selecting a standard motor or constant-torque motor, thermal
characteristic and motor constants of each motor are set.
80
Motor capacity
9999
0.1–55 kW
Set the applied motor capacity.
9999
V/F Control
81
Number of motor poles
9999
2/4/6/8/10
Set the number of motor poles.
9999
V/F Control
800
Control method selection
20
20
Advanced magnetic flux vector control
햳
30
General-purpose magnetic flux vector control
햳
NOTES
If the following conditions are not satisfied, select V/F control since malfunction such as insuffi-
cient torque and uneven rotation may occur.
●
The motor capacity should be equal to or one rank lower than the inverter capacity. (Note that
the capacity should be 0.1 kW or more.)
●
Motor to be used is any of Mitsubishi standard motor, high efficiency motor (SF-JR, SF-HR
0.2 kW or more) or Mitsubishi constant-torque motor (SF-JRCA four-pole, SF-HRCA 0.4 kW to
15 kW). When using a motor other than the above (other manufacturer's motor), perform
offline auto tuning without fail.
Single-motor operation (one motor run by one inverter) should be performed.
The wiring length from inverter to motor should be within 30 m. (Perform offline auto tuning in
the state where wiring work is performed when the wiring length exceeds 30 m.)
AD MFVC
AD MFVC
AD MFVC
GP MFVC
GP MFVC
GP MFVC
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......