Operation
Operation panel
FR-E700 SC EC/ENE
4 - 13
4.3.4 Operation
lock
Operation using the digital dial and key of the operation panel can be made invalid to prevent pa-
rameter change and unexpected start and stop.
Operation lock
●
Set "10" or "11" in Pr. 161, then press the MODE key for 2 s to make the digital dial key operation
invalid.
●
When the digital dial and key operation is made invalid, "HOLD" appears on the operation panel.
●
When the digital dial and key operation is invalid, "HOLD" appears if the digital dial or key
operation is performed. (When the digital dial or key operation is not performed for 2 s, the
monitor display appears.)
Operation unlock
To make the digital dial and key operation valid again, press the MODE key for 2 s.
NOTES
The STOP/RESET key is valid even in the operation lock status.
Set "0" (extended mode parameter valid) in Pr. 160 "User group read selection".
Set "10" or "11" (key lock mode valid) in Pr. 161 "Frequency setting/key lock operation selection".