Adjust the output torque (current) of the motor
Parameter
6 - 26
6.2
Adjust the output torque (current) of the motor
6.2.1
Manual torque boost (Pr. 0, Pr. 46)
You can compensate for a voltage drop in the low-frequency region to improve motor torque re-
duction in the low-speed range. Motor torque in the low-frequency range can be adjusted to the
load to increase the starting motor torque.
Switch-over between parameters 0 and 46 is possible via the RT input signal.
The above parameter can be set when Pr. 160 = 0.
Purpose
Parameter that must be set
Refer to
Section
Set starting torque manually
Manual torque boost
Pr. 0, Pr. 46,
Automatically control output current
according to load
General-purpose magnetic flux
vector control
Pr. 71, Pr. 80
Compensate for motor slip to secure
low-speed torque
Slip compensation
Pr. 245–Pr. 247 6.2.3
Limit output current to prevent
inverter trip
Stall prevention operation
Pr. 22, Pr. 23,
Pr. 66, Pr. 156,
Pr. 157
Pr.
No.
Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
0
Torque boost
FR-D720S-008SC to
042SC,
FR-D740-022SC or less
6%
0–30%
Set the output voltage at
0Hz as %.
3
19
71
178–182
Base frequency
Base frequency
voltage
Applied motor
Input terminal
function selection
FR-D720S-070SC and
100SC,
FR-D740-036SC to
080SC
4%
FR-D740-120SC and
160SC
3%
46
Second torque
boost
9999
0–30%
Set the torque boost value
when the RT signal is on.
9999
Without second torque
boost
V/F
V/F
V/F
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......