195
Communication operation and setting
7) Error code
If any error is found in the data received by the drive unit, its definition is sent back to the computer together with the
NAK code.
(5) Response time
[Formula for data sending time]
Communication specifications
Data check time
Error
Code
Error Item
Error Description
Drive Unit Operation
H0
Computer NAK error
The number of errors detected consecutively in communication request
data from the computer is greater than allowed number of retries.
Brought to trip (E. PUE)
if error occurs
continuously more than
the allowable number of
retry times.
H1
Parity error
The parity check result does not match the specified parity
H2
Sum check error
The sum check code in the computer does not match that of the data
received by the drive unit.
H3
Protocol error
The data received by the drive unit has a grammatical mistake.
Alternatively, data reception is not completed within the predetermined
time. CR or LF is not as set in the parameter.
H4
Framing error
The stop bit length differs from the initial setting.
H5
Overrun error
New data has been sent by the computer before the drive unit completes
receiving the preceding data.
H6
—
—
—
H7
Character error
The character received is invalid (other than 0 to 9, A to F, control code).
Does not accept
received data but is not
brought to trip.
H8
—
—
—
H9
—
—
—
HA
Mode error
Parameter write was attempted in other than the computer link operation
mode, when operation command source is not selected or during drive
unit operation.
Does not accept
received data but alarm
does not occur.
HB
Instruction code
error
The specified command does not exist.
HC
Data range error
Invalid data has been specified for parameter write, speed setting, etc.
HD
—
—
—
HE
—
—
—
HF
Nomal (no error)
—
—
1
Number of data characters
Communication
(Total number of bits) = data sending time (s)
(Refer to the following.)
Communication speed (bps)
Name
Number of
Bits
Item
Check Time
Stop bit length
1 bit
2 bits
Various monitors, operation command, speed
setting (RAM)
< 12ms
Data length
7 bits
8 bits
Parameter read/write, speed setting
(EEPROM)
< 30ms
Parity check
Present
1 bit
Parameter clear/all clear
< 5s
Absent
0
Reset command
No answer
In addition to the above, 1 start bit is necessary.
Minimum number of total bits.................9 bits
Maximum number of total bits................12 bits
10ms or more necessary
Computer
Drive unit
Drive unit
Computer
Data sending time (refer to the following formula.)
(Setting 10ms)
(depends on the instruction
code (see the following table))
Drive unit data processing time = Waiting time + Data check time
Data sending time (refer to the following formula.)
Time