143
Motor noise, EMI measures, mechanical resonance
4.15 Motor noise, EMI measures, mechanical resonance
4.15.1 PWM carrier frequency and soft-PWM control (Pr. 72, Pr. 240, Pr. 260)
(1) PWM carrier frequency changing
(Pr. 72)
You can change the PWM carrier frequency of the inverter.
Changing the PWM carrier frequency produces an effect on avoiding the resonance frequency of a mechanical system or
motor or on EMI measures or on leakage current reduction caused by the PWM switching.
(2) Soft-PWM control
(Pr. 240)
Soft-PWM control is a control method that changes the motor noise from a metallic tone into an unoffending complex tone.
(3) PWM carrier frequency automatic reduction function
(Pr. 260)
When continuous operation is performed at 85% or more of the inverter rated current with the carrier frequency of the
inverter set to 3kHz or more (
Pr. 72
≥
"3"), the carrier frequency is automatically reduced to 2kHz to protect the output
transistor of the inverter. (Motor noise increases, but it is not a failure)
When
Pr. 260
= "0" (initial value), the carrier frequency becomes constant (
Pr. 72
setting) independently of the load,
making the motor sound uniform.
Note that continuous operation should be performed at less than 85% of the inverter rating.
Purpose of Use
Parameter that should be Set
Refer to Page
Reduction of the motor noise
Measures against EMI and leakage
currents
Carrier frequency and
Soft-PWM selection
Pr. 72, Pr. 240, Pr. 260
Reduce mechanical resonance
Speed smoothing control
Pr. 653
You can change the motor sound.
Parameter
Number
Name
Initial Value
Setting Range
Description
72 *
PWM frequency selection
1
0 to 15
You can change the PWM carrier frequency.
The setting is in [kHz].
Note that 0 indicates 0.7kHz and 15
indicates 14.5kHz.
240 *
Soft-PWM operation
selection
1
0
Soft-PWM is invalid
1
When
Pr. 72
= "0 to 5", soft-PWM is valid.
260
PWM frequency
automatic switchover
0
0
PWM carrier frequency is constant
independently of load.
When the carrier frequency is set to 3kHz
or more (
Pr. 72
≥
"3"), perform continuous
operation at less than 85% of the rated
inverter current.
1
Decreases PWM carrier frequency
automatically when load increases.
The above parameters can be set when
Pr.160 Extended function display selection
= "0".
* The parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
NOTE
Decreasing the PWM carrier frequency effect on EMI measures and on leakage current reduction, but increases
motor noise.
When PWM carrier frequency is set to 1kHz or less (
Pr.72
≤
1), fast response current limit may function prior to stall
prevention operation due to increase in ripple currents, resulting in insufficient torque. In such case, set fast-
response current limit operation invalid using
Pr. 156 Stall prevention operation selection
.
Parameters referred to
Pr. 156 Stall prevention operation selection
Содержание FR-D700 Series
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 57: ...46 MEMO ...
Страница 262: ...258 MEMO ...
Страница 276: ...272 MEMO ...
Страница 283: ...279 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 287: ...283 MEMO ...
Страница 289: ......