(M) Monitor display and monitor output signal
108
Fault output signals (ALM, ALM2)
NOTE
• For the details of converter unit faults, refer to
.
5.4.3
Detection of control circuit temperature
Control circuit temperature monitor
• The operation panel can be used to monitor the temperature of the control circuit board within the range of 0 to 100°C.
• The range becomes -20 to 100°C by setting the display with a minus sign in
Pr.290 Monitor negative output selection
.
Control circuit temperature detection (Pr.663, Y207 signal)
• The Y207 signal can be output when the control circuit temperature reaches the
Pr.663
setting or higher.
• For the Y207 signal, set "207 (positive logic) or 307 (negative logic)" in one of
Pr.190 to Pr.195 (Output terminal function
selection)
to assign the function to the output terminal.
NOTE
• The Y207 signal is turned OFF when the control circuit temperature becomes 5°C or more lower than the
Pr.663
setting.
• Changing the terminal assignment using
Pr.190 to Pr.195 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.195 (Output terminal function selection)
Pr.290 Monitor negative output selection
• The Fault (ALM, ALM2) signals are output when the converter
unit protective function is activated.
• The ALM2 signal stays ON during the reset period after the fault
occurs.
• To use the ALM2 signal, set "94 (positive logic) or 194 (negative
logic)" in any of
Pr.190 to Pr.195 (Output terminal function
selection)
to assign the function to the output terminal.
• The ALM signal is assigned to the A1B1C1 contacts in the initial
status.
The temperature of the control circuit board of the converter unit can be monitored, and a signal can be output
according to the predetermined temperature setting.
Pr.
Name
Initial value Setting range
Description
663
M060
Control circuit
temperature signal
output level
0°C
0 to 100°C
Set the temperature where the Y207 signal turns ON.
ON
Reset processing
(about 1s)
OFF
ON
ON OFF
Reset ON
ALM
ALM2
RES
OFF
Converter unit fault occurrence
(trip)