5. PARAMETERS
5.2 (E) Environment setting parameters
• When setting dial and key operations are disabled, "
" appears on the operation panel. If setting dial or key
operation is attempted while dial and key operations are disabled, "
" appears. (When a setting dial or key
operation is not performed for 2 seconds, the monitor display appears.)
• To enable the setting dial and key operation again, press
for 2 seconds.
NOTE
• Even if setting dial and key operations are disabled, the monitor indicator and
are enabled.
5.2.6
Using a 600 VAC power supply
To use a 600 VAC power supply, change the voltage protection level.
• To use a 600 VAC power supply, set
Pr.977 Input voltage mode selection
= "2". The setting is applied after converter
reset. Parameter clear or All parameter clear must be performed after resetting the converter unit.
• Setting
Pr.977
= "2" changes the voltage protection level to the one for the 600 VAC class.
5.2.7
Parameter write selection
Whether to enable the writing to various parameters or not can be selected. Use this function to prevent parameter values from
being rewritten by misoperation.
•
Pr.77
can be set any time. (Setting through communication is unavailable.)
Disabling parameter write (Pr.77 = "1")
• Parameter write, Parameter clear, and All parameter clear are disabled. (Parameter read is enabled.)
• The following parameters can be written even if
Pr.77
= "1".
Writing parameters (Pr.77 = "2")
• These parameters can always be written.
Pr.
Name
Initial value
Setting range
Description
977
E302
Input voltage mode selection
0
0
690 VAC class voltage protection level
2
600 VAC class voltage protection level
Pr.
Name
Initial value
Setting range
Description
77
E400
Parameter write selection
2
1
Parameter writing is disabled.
2
Parameter writing is enabled
Pr.
Name
75
Reset selection/disconnected PU detection/reset
limit
77
Parameter write selection
296
Password lock level
297
Password lock/unlock
997
Fault initiation
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...