166
8. SPECIFICATIONS
8.1 Converter unit rating
8
SPECIFICATIONS
This chapter explains the specifications of this product.
Always read the instructions before use.
8.1
Converter unit rating
690 VAC power input
*1
The percentage of the overload current rating is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow
time for the converter unit and the inverter to return to or below the temperatures under 100% load.
*2
The converter unit output voltage varies according to the input power supply voltage and the load. The maximum point of the voltage waveform
at the output side of the converter unit is approximately the power supply voltage multiplied by
.
*3
The power supply capacity is the value at the rated output current. The input power impedances (including those of the input reactor and cables)
affect the value.
*4
The permissible voltage imbalance ratio is 3% or less. (Imbalance ratio = (highest voltage between lines - average voltage between three lines )
/ average voltage between three lines × 100)
*5
Values measured 1 m in front of the converter unit and 1.6 m from the floor.
575 VAC power input
*1
The percentage of the overload current rating is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow
time for the converter unit and the inverter to return to or below the temperatures under 100% load.
*2
The converter unit output voltage varies according to the input power supply voltage and the load. The maximum point of the voltage waveform
at the output side of the converter unit is approximately the power supply voltage multiplied by
.
Model FR-CC2-N[]
450K
500K
560K
630K
Applicable motor capacity (kW)
450
500
560
630
Outpu
t
Overload current rating
150% 60 s, 200% 3 s at surrounding air
temperature of 40°C
110% 60 s, 120% 3 s at
surrounding air
temperature of 40°C
Pow
er supply
612
680
773
855
Rated input current (A)
512
569
647
715
Rated input AC voltage/frequency
Three-phase 600 V to 690 V 50/60 Hz
Permissible AC voltage fluctuation
Three-phase 540 V to 759 V 50/60 Hz
Permissible frequency fluctuation
±5%
Protective structure (IEC 60529)
Open type (IP00)
Cooling system
Forced air
DC reactor
Built-in
Noise level (dB)
74
74
74
74
Approx. mass (kg)
237
241
245
248
Model FR-CC2-N[]
450K
500K
560K
630K
Applicable motor capacity (kW)
355
400
450
500
Output
Overload current rating
150% 60 s, 200% 3 s at surrounding air
temperature of 40°C
110% 60 s, 120% 3 s at
surrounding air
temperature of 40°C
Power supply
510
567
644
712
Rated input current (A)
512
569
647
715
Rated input AC voltage/frequency
Three-phase 525 V to 600 V 50/60 Hz
Permissible AC voltage fluctuation
Three-phase 472 V to 660 V 50/60 Hz
Permissible frequency fluctuation
±5%
Protective structure (IEC 60529)
Open type (IP00)
Cooling system
Forced air
DC reactor
Built-in
Noise level (dB)
74
74
74
74
Approx. mass (kg)
237
241
245
248
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...