5. PARAMETERS
5.7 (N) Communication operation parameters
1
2
3
4
5
6
7
8
9
10
• Error detection of message data
The following errors are detected in message data from the master. The inverter output is not shut off even if an error is
detected.
Error check items
NOTE
• The LF signal can be assigned to an output terminal by setting
Pr.190 to Pr.195 (Output terminal function selection)
.
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
MODBUS register
• The following shows the MODBUS registers for system environment variables (read/write), real time monitor items (read),
parameters (read/write), fault history data (read/write), and model information monitor items (read).
• System environment variables
*1
Settings in the communication parameters are not cleared.
• Converter unit status
*2
The signal within parentheses ( ) is the initial status. The description changes depending on the setting of
Pr.190 to Pr.195 (Output terminal
function selection)
).
Error item
Error description
Converter unit operation
Parity error
The data received by the converter unit has different
parity from the specified one (
Pr.334
setting).
When this error occurs,
Pr.343
is
incremented by one.
When this error occurs, the LF signal is
output.
Framing error
The data received by the converter unit has a different
stop bit length from the specified one (
Pr.334
setting).
Overrun error
The next data has been sent by the master before the
converter unit completes receiving the preceding data.
Message frame error
The data length of the message frame is checked, and an
error is generated if the received data length is less than
4 bytes.
CRC check error
An error is generated if the data in the message frame
does not match the calculation result.
Register
Definition
Read/write
Remarks
40002
Converter reset
Write
Any value
40003
Parameter clear
Write
Set H965A.
40004
All parameter clear
Write
Set H99AA.
40006
Parameter clear
Write
Set H5A96.
40007
All parameter clear
Write
Set HAA99.
40009
Converter unit status
Read/write
Refer to the following.
Bit
Description
0
RDB (Inverter operation enable (NC contact))
1
0
2
0
3
RDA (Inverter operation enable (NO contact))
4
RSO (Inverter reset)
5
IPF (Instantaneous power failure/
undervoltage)
6
FAN (Fan fault output)
7
ABC1 (Fault)
8
0
9
0
10
0
11
0
12
0
13
0
14
0
15
Fault occurrence
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...