111
5. PARAMETERS
5.7 (N) Communication operation parameters
1
2
3
4
5
6
7
8
9
10
c. Reply data from the converter unit to the computer (No data error detected)
c. Reply data from the converter unit to the computer (Data error detected)
e. Transmission data from the computer to the converter unit when reading data
*1
Indicates a control code.
*2
Specifies the converter unit station numbers in the range of H00 to H1F (stations 0 to 31) in hexadecimal.
*3
Set the delay time. When
Pr.123 PU communication waiting time setting
or
Pr.337 RS-485 communication waiting time setting
is set to
other than "9999", create the communication request data without "delay time" in the data format. (The number of characters decreases by 1.)
*4
CR/LF code: When a computer transmits data to the converter unit, some computers automatically provide either one or both of the codes CR
(carriage return) and LF (line feed) at the end of a data group. In this case, setting must be also made on the converter unit according to the
computer. Use
Pr.124
or
Pr.341
for the CR+LF code setting.
Data definitions
• Control code
• Converter unit station number
Specify the station number of the converter unit which communicates with the computer.
• Instruction code
Specify the processing request, for example, operation or monitoring, given by the computer to the converter unit.
Therefore, the operation or monitoring an item is enabled by specifying the corresponding instruction code. (Refer to
• Data
Read/write data such as parameters transmitted from/to the converter unit. The definitions and ranges of set data are
determined in accordance with the instruction codes. (Refer to
.)
• Time delay
Format
Number of characters
1
2
3
4
5
6
7
8
9
10
11
12
13
E
STX
Converter unit
station number
Read data
ETX
Sum check
E1
STX
Converter unit
station number
Read data
ETX
Sum check
E2
STX
Converter unit
station number
Read data (model information / capacity)
Sum check
Format
Number of characters
1
2
3
4 to 23
24
25
26
27
E3
STX
Converter unit
station number
Read data (model information / converter unit
model)
ETX
Sum check
Format
Number of characters
1
2
3
4
5
D
Converter unit
station number
Error
code
Format
Number of characters
1
2
3
4
C (No data error
detected)
Converter unit
station number
F (Data error
detected)
Converter unit
station number
Signal name
ASCII code
Description
STX
H02
Start Of Text (Start of data)
ETX
H03
End Of Text (End of data)
ENQ
H05
Enquiry (Communication request)
ACK
H06
Acknowledge (No data error detected)
LF
H0A
Line Feed
CR
H0D
Carriage Return
NAK
H15
Negative Acknowledge (Data error detected)
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...