INSTALLATION INSTRUCTIONS FOR COMPLIANCE WITH UL

Install the FR-ABR brake resistors as follows:

The resistor may be mounted horizontally or vertically, depending on a

suitable surface location.

When the resistor is mounted externally to the enclosure housing the

inverter, install a solid Type 1 enclosure at least 8 times the volume size

of the resistor that incorporates mesh or perforated steel type ventilation

openings at each end of the resistor. Note, the vent openings shall not be

greater than 10 mm diameter.

Secure the enclosure to a non-combustible surface only, such as metal or

concrete.

Mount the resistor inside the Type 1 enclosure and wire it in accordance

with the NEC for North America installations or any other local codes.

Note, when the resistor and inverter are mounted together within a suitable

enclosure, the mesh covering is not required. Please take care that the

Inverter unit / resistor internal enclosure ambient does not exceed 50 deg. C.

Enclosure surface presents a possible burn hazard. After installation, the

following marking in minimum 3 mm (1/8 in.) sized lettering shall be provided

on the enclosure where visible:

CAUTION : HOT SURFACE. TO REDUCE RISK OF BURN - DO NOT TOUCH.

FR-ABR_UL.book  3 ページ  2004年3月16日 火曜日 午後3時55分

Содержание FR-ABR-(H)0.4K

Страница 1: ...TRANSISTORIZED INVERTER INSTRUCTION MANUAL FR ABR H 0 4K to 15K HIGH DUTY BRAKE RESISTOR F FR ABR_UL book 1 ページ 2004年3月16日 火曜日 午後3時55分 ...

Страница 2: ...ipment safety information and instructions In this manual the safety instruction levels are classified into WARNING and CAUTION Denotes that incorrect handling may cause hazardous conditions resulting in death or severe injury Denotes that incorrect handling may cause hazardous conditions resulting in medium or slight injury or may cause physical damage only Note that even the level may lead to a ...

Страница 3: ... to the correct terminals Otherwise damage etc may occur While power is on or for some time after power off do not touch the brake resistor as it is hot Touching it can cause burns CAUTION Transport products in a correct manner according to their weights Not doing so can cause injury Install the product in a place secure enough to withstand its weight according to the instruction manual WARNING Do...

Страница 4: ...cure the enclosure to a non combustible surface only such as metal or concrete Mount the resistor inside the Type 1 enclosure and wire it in accordance with the NEC for North America installations or any other local codes Note when the resistor and inverter are mounted together within a suitable enclosure the mesh covering is not required Please take care that the Inverter unit resistor internal e...

Страница 5: ...0W 0 4K FR A024 0 4K FR S520E 0 4K FR ABR 0 75K FR A520 0 75K FR E520 0 75K C FR E520S 0 75K FR E510W 0 75K FR A024 0 75K FR S520E 0 75K FR ABR 2 2K FR A520 1 5K FR A520 2 2K FR E520 1 5K C FR E520 2 2K C FR V520 1 5K FR V520 2 2K FR A024 1 5K FR A024 2 2K FR S520E 1 5K FR S520E 2 2K FR ABR 3 7K FR A520 3 7K FR E520 3 7K C FR V520 3 7K FR A024 3 7K FR S520E 3 7K FR ABR 5 5K FR A520 5 5K FR E520 5 ...

Страница 6: ...0 2 2K FR E540 2 2K C FR V540 2 2K FR A044 2 2K FR ABR H3 7K FR A540 3 7K FR E540 3 7K C FR V540 3 7K FR A044 3 7K FR ABR H5 5K FR A540 5 5K FR E540 5 5K C FR V540 5 5K FR ABR H7 5K FR A540 7 5K FR E540 7 5K C FR V540 7 5K FR ABR H11K FR V540 11K FR ABR H15K FR V540 15K Note indicates alpha numeric combination High Duty Brake Resistor Model Applicable Inverter Models FR ABR_UL book 2 ページ 2004年3月16...

Страница 7: ...eads of the resistor and any other wiring Install the resistor in a place with good heat dissipation The reason for this is that the surface temperature of the resistor may exceed 360 C in an operation pattern where the resistor is used frequently To increase the heat dissipation effect we recommend you to install the resistor on a metal surface outside the enclosure Provide an enclosure with good...

Страница 8: ...inverter does not have the PX terminals Refer to the instruction manual of the inverter 2 For the 400V class power supply install a voltage reducing transformer 3 When using the H 11K or 15K install a thermal relay Refer to the following table for the thermal relay model number and to the following diagram for connection Capacity Thermal relay OCR Contact Rating 11K 15K TH N20CXHZ 11A AC110V 5A AC...

Страница 9: ...ting of inverter parameters 1 The parameter setting method varies with the inverter series Refer to the instruction manual of the inverter CAUTION 1 The high duty brake resistor cannot be used with a brake unit high power factor converter power return converter built in brake etc 2 Twist the leads of the high duty brake resistor when increas ing their length 2m or more The wire size used should be...

Страница 10: ... Ω Crimping Terminal Unit mm W W1 W2 D H A1 A2 B d B1 d1 200V Class FR ABR 0 4K 140 125 100 40 21 200 7 0 4 3 7 0 4 3 FR ABR 0 75K 215 200 175 40 21 100 FR ABR 2 2K 1 240 225 200 50 26 60 FR ABR 3 7K 215 200 175 61 33 40 FR ABR 5 5K 335 320 295 61 33 25 9 5 5 3 9 5 5 3 FR ABR 7 5K 400 385 360 80 40 20 400V Class FR ABR H0 4K 115 100 75 40 21 1200 7 0 4 3 7 0 4 3 FR ABR H0 75K 140 125 100 40 21 700...

Страница 11: ...mensions Unit mm Resistance Ω Crimping Terminal Unit mm W W1 W2 d 200V Class FR ABR 11K 400 385 360 13 6 4 FR ABR 15K 1 300 285 260 18 8 4 400V Class FR ABR H11K 400 385 360 52 6 4 FR ABR H15K 2 300 285 260 18 8 4 W W1 1 W2 5 3 700 20 0 100 50 2 5 φd 12 A1 A1 φ5 3 9 5 A2 A2 80 5 1 Glass braided cable 2 0mm2 white FR ABR_UL book 7 ページ 2004年3月16日 火曜日 午後3時55分 ...

Страница 12: ... 150Ω 155W FR ABR 7 5K 20Ω 340W FR ABR H5 5K 110Ω 185W FR ABR 11K 13Ω 560W FR ABR H7 5K 75Ω 340W FR ABR 15K 9Ω 1 805W FR ABR H11K 52Ω 530W 1 When two resistors are connected in series FR ABR H15K 36Ω 2 870W 2 When two resistors are connected in parallel 200V Class 400V Class 0 20 40 60 80 100 120 140 10 20 30 50 70 100 200 300 500 700 1000 2000 3000 5000700010000 2 2K 0 75K 0 4K 5 5K 3 7K 15000 15...

Страница 13: ... inverters Instructions for wiring Apr 2002 IB NA 66891 C FR ABR 11K FR ABR 15K Aug 2002 IB NA 66891 D FR ABR H11K FR ABR H15K Instructions for wiring Oct 2003 IB NA 66891 E UL compliance Mar 2004 IB NA 66891 F OUTLINE DIMENTIONS OUTLINE DIMENSION DRAWINGS Partial Additions Additions Additions Partial Addition Additions Modifications FR ABR_UL book 1 ページ 2004年3月16日 火曜日 午後3時55分 ...

Страница 14: ...u SIA POWEL LATVIA Lienes iela 28 LV 1009 Riga Phone 371 784 2280 Fax 371 784 2281 e mail utu utu lv UAB UTU POWEL LITHUANIA Savanoriu Pr 187 LT 2053 Vilnius Phone 370 0 52323 101 Fax 370 0 52322 980 e mail powel utu lt EUROPEAN REPRESENTATIVES Intehsis Srl MOLDOVA Cuza Voda 36 1 81 MD 2061 Chisinau Phone 373 0 2 562 263 Fax 373 0 2 562 263 e mail intehsis mdl net Getronics b v NETHERLANDS Control...