(N) Operation via communication and its settings
Parameters
5 - 626
5.15.3
Initial setting of operation via communication
Set the action when the inverter is performing operation via communication.
●
Set the communication protocol. (Mitsubishi inverter protocol/Modbus® RTU protocol)
●
Set the action at fault occurrence or at writing of parameters
The setting is available only when a communication option is installed.
During communication using the communication option, "E.OP1" or "E.1" is displayed.
FR-A800-E: The parameter is used when the CC-Link IE Field Network Basic is selected (refer to page
5-802).
FR-A800-E: The parameter setting is valid when Pr. 1431 "Ethernet signal loss detection function
selection" = "3" or Pr. 1432 "Ethernet communication check time interval"
≠
"9999" during Ethernet
communication.
Pr.
Name
Initial
value
Setting
range
Description
549
N000
Protocol selection
0
0
Mitsubishi inverter protocol (computer link)
1
Modbus® RTU protocol
342
N001
Communication EEPROM
write selection
0
0
Parameter values written by communication are written to
the EEPROM and RAM.
1
Parameter values written by communication are written to
the RAM.
349
Communication reset
selection
0
0
Enables the error reset function in any operation mode.
1
Enables the error reset function only in the Network
operation mode.
500
Communication error
execution waiting time
0 s
0 to 999.8 s
Set the time from when the communication line error
occurs until the inverter starts the operation for the
communication error (when a communication option is
used).
501
Communication error
occurrence count display
0
0
Displays the communication error occurrence count
(when a communication option is used).
502
N013
Stop mode selection at
communication error
0
0
At fault occurrence
At fault removal
Coasts to stop
"E.SER" (FR-A800-E: "E.EHR")
display
ALM signal output
Stays stopped
"E.SER" (FR-A800-E: "E.EHR")
display
1
Deceleration stop
"E.SER" (FR-A800-E: "E.EHR")
display after stop
ALM signal output after stop
Stays stopped
"E.SER" (FR-A800-E: "E.EHR")
display
2
Deceleration stop
"E.SER" (FR-A800-E: "E.EHR")
display after stop
Automatic restart function
3
Operation continued at the
set frequency of Pr. 779
Normal operation
4
Operation continued at the
set frequency of Pr. 779
"CF" display
Normal operation
779
N014
Operation frequency
during communication
error
9999
0 to 590 Hz
Set the frequency to be run at a communication error
occurrence.
9999
The motor runs at the frequency used before the
communication error.
NOTE
For details regarding the stop mode selection at communication error for the different settings of
Pr. 502 refer to tab. 5-272.
Содержание FR-A820-00046 (0.4K)
Страница 2: ......
Страница 4: ......
Страница 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Страница 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Страница 1110: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1188: ...EC Declarations of Conformity Appendix A 48 A 7 EC Declarations of Conformity A 7 1 FR A820 FR A840 FR A842 series ...
Страница 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1190: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Страница 1192: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1194: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1196: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Страница 1198: ...EC Declarations of Conformity Appendix A 58 ...
Страница 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Страница 1200: ...EC Declarations of Conformity Appendix A 60 ...
Страница 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Страница 1202: ...EC Declarations of Conformity Appendix A 62 ...
Страница 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Страница 1204: ...EC Declarations of Conformity Appendix A 64 ...
Страница 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Страница 1206: ...EC Declarations of Conformity Appendix A 66 ...
Страница 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Страница 1208: ...EC Declarations of Conformity Appendix A 68 ...
Страница 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Страница 1210: ...EC Declarations of Conformity Appendix A 70 ...
Страница 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Страница 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Страница 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Страница 1214: ...EC Declarations of Conformity Appendix A 74 ...
Страница 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Страница 1216: ...EC Declarations of Conformity Appendix A 76 A 7 3 Frequency inverters with option unit FR A8NP ...
Страница 1217: ......