109
OBJECT DICTIONARY
8
8.3.15 (Index 4012h) Set Frequency (w) / Set Speed (w)
<Detail>
Perform frequency (speed) setting to the inverter in 0.01Hz (1r/min) increments.
When index 4001h set frequency (w)/output frequency (r) set speed (w)/running speed (r) are set at the
same time (when written by SDO and PDO simultaneously), the value written later has precedence.
Sub Index
Item
Description
00h
Name
Number of Entries
Data type
UNSIGNED8 (8 bit unsigned)
Default value
2
Unit
Access attribute
Read Only
Availability of mapping to PDO Disable
01h
Name
Set Frequency (w)
Data type
UNSIGNED16 (16 bit unsigned)
Default value
Unit
0.01Hz (frequency)
Access attribute
Write Only
Availability of mapping to PDO Enable
02h
Name
Set Speed (w)
Data type
UNSIGNED16 (16 bit unsigned)
Default value
Unit
1r/min (speed)
Access attribute
Write Only
Availability of mapping to PDO Enable
REMARKS
Refer to
page 34
conversion of set speed and running speed.
A7NCA.book 109 ページ 2006年7月3日 月曜日 午前9時48分