background image

24

A APPENDIX

A.1 Instructions for Compliance with the European Directives

A.1.1 EMC Directive

Our view of transistorized inverters for the EMC Directive
A transistorized inverter is a component designed for installation in an enclosure and for use with the other equipment to
control the equipment/device. Therefore, we understand that the EMC Directive does not apply directly to transistorized
inverters. For this reason, we do not place the CE mark on the transistorized inverters. (The CE mark is placed on
inverters in accordance with the Low Voltage Directive.) CEMEP

Compliance
We understand that the general-purpose inverters are not covered directly by the EMC Directive. However, the EMC
Directive applies to machines/equipment into which inverters have been incorporated, and these machines and
equipment must carry the CE marks. EMC Installation Guidelines BCN-A21041-202

Outline of installation method
Install an inverter using the following methods:
–  Use the inverter with an European Standard-compliant noise filter.
– For wiring between the inverter and motor, use shielded cables or run them in a metal piping and ground the cables on

the inverter and motor sides with the shortest possible distance.

– Insert a line noise filter and ferrite core into the power and control lines as required.

Full information including the European Standard-compliant noise filter specifications are written in the technical
information "EMC Installation Guidelines" (BCN-A21041-202). Please contact your sales representative.

A.1.2 Low Voltage Directive

We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard
EN 61800-5-1) and placed the CE mark on the inverters.

Outline of instructions

Do not use a residual current operated protective device (RCD) as an electric shock protector without connecting the
equipment to the earth. Connect the equipment to the earth securely.

Wire the earth terminal independently. (Do not connect two or more cables to one terminal.) 

Use the cable sizes on 

page 6

 at the ambient temperature indicated there.

If the ambient temperature is different, select appropriate wire according to EN60204 ANNEX C TABLE 5.

When tightening the screw, be careful not to damage the threads.

For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on 

page 6

.

Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard. 

Use the residual current operated protective device (RCD) of type B (breaker which can detect both AC and DC).
However, be aware that also AC/DC sensitive earth leakage circuit breakers can be activated when turning the main
power on and off and that this behaviour can be improved through the use of AC/DC sensitive earth leakage circuit
breakers with adapted triggering curve designed for the inverter. If not, provide double or reinforced insulation between
the inverter and other equipment, or put a transformer between the main power supply and inverter.

Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the
power supply), overvoltage category III (usable with the earthed-neutral system power supply, 400 V class only)
specified in IEC664.

To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.

On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.

The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30 V DC, 0.3 A. (Relay outputs are
basically isolated from the inverter internal circuit.)

Control circuit terminals on 

page 4

 are safely isolated from the main circuit

Environment

During Operation

In Storage

During Transportation

Ambient temperature

10°C to + 50°C

20°C to +65°C

20°C to +65°C

Ambient humidity

90% RH or less

90% RH or less

90% RH or less

Maximum altitude

1000m

1000m

10000m

Содержание FR-A741-11K

Страница 1: ...MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC INDUSTRIAL AUTOMATION Frequency Inverter Installation Guideline FR A741 5 5K to 55K Art No 224739 08 04 2009 Version A ...

Страница 2: ......

Страница 3: ... product until you have a full knowledge of the equipment the safety information and the instructions Please forward this manual to the end user 1 2 3 4 5 6 INSTALLATION OF THE INVERTER AND INSTRUCTIONS 1 OUTLINE DIMENSION DRAWING 3 WIRING 4 PRECAUTIONS FOR THE USEOF THE INVERTER 9 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER 11 PARAMETER 12 TROUBLESHOOTING 22 APPENDIX 24 7 A ...

Страница 4: ... applications please contact your nearest Mitsubishi sales representative Although this product was manufactured under conditions of strict quality control you are strongly advised to install safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product are likely to cause a serious accident Please do not use this product for loads other than three phase...

Страница 5: ... wet hands You may get an electric shock When measuring the main circuit capacitor capacity the DC voltage is applied to the motor for 1s at powering off Never touch the motor terminal etc right after powering off to prevent an electric shock Install the inverter on a nonflammable wall without holes so that nobody can touch the inverter heatsink on the rear side etc Mounting it to or near combusti...

Страница 6: ...e of the inverter The electronic thermal relay function does not guarantee protection of the motor from overheating Do not use a magnetic contactor on the inverter input for frequent starting stopping of the inverter Use a noise filter to reduce the effect of electromagnetic interference and follow the accepted EMC procedures for proper installation of frequency inverters Otherwise nearby electron...

Страница 7: ... number 5 5 to 55 Indicate inverter capacity kW Capacity plate example Rating plate example Capacity plate Rating plate Serial number Inverter type Inverter type Input rating Output rating Serial number CAUTION When encasing multiple inverters install them in parallel as a cooling measure Install the inverter vertically vertical Refer to the clearances below Ambient air temperature and humidity Cl...

Страница 8: ...environment meets following specifications Ambient temperature 10 C to 50 C non freezing Ambient humidity 90 RH or less non condensing Atmosphere Free from corrosive and explosive gases free from dust and dirt Maximum altitude Maximum 1000 m above sea level Vibration 5 9m s or less CAUTION Install the inverter on a strong surface securely and vertically with bolts Leave enough clearances and take ...

Страница 9: ... 5 5K 250 190 470 454 425 270 FR A741 7 5K FR A741 11K 300 220 600 575 540 294 FR A741 15K FR A741 18 5K 360 260 600 575 535 320 FR A741 22K FR A741 30K 450 350 700 675 635 340 FR A741 37K 470 370 700 670 630 368 FR A741 45K FR A741 55K 600 480 900 870 830 405 W1 W H1 H D H2 ...

Страница 10: ...input common Sink 3 JOG terminal can be used as pulse train input terminal Use Pr 291 to select JOG pulse 24 V DC power supply max 100 mA load current Contact input common Source Common for external power supply transistor Frequency setting signal Analog Auxiliary input Terminal 4 input Current input 0 5V DC 0 10V DC 4 20mA DC 0 to 10V DC 0 to 20mA DC 0 to 5V DC 0 to 5V DC 0 to 10V DC PU connector...

Страница 11: ... of the inverter Doing so will damage the inverter Connect the motor to U V W At this time turning on the forward rotation switch signal rotates the motor in the clockwise direction when viewed on the motor shaft Screw size M4 Jumper Charge lamp Motor Power supply M 3 L1 L2 L3 Screw size M4 Jumper Charge lamp Power supply Screw size M5 Motor Screw size M4 M 3 L1 L2 L3 Screw size M4 Charge lamp Jum...

Страница 12: ...0K 22 22 14 4 21 1 4 21 1 25 25 16 FR A741 37K 22 22 14 4 21 1 4 21 1 25 25 16 FR A741 45K 38 38 22 1 42 4 2 33 6 50 50 25 FR A741 55K 60 60 22 1 0 42 4 53 4 50 50 25 1 The recommended cable size is that of the HIV cable 600V class 2 vinyl insulated cable with continuous maximum permissible temperature of 75 C Assumes that the ambient temperature is 50 C or less and the wiring distance is 20m or l...

Страница 13: ...llowing measures Use a 400V class inverter driven insulation enhanced motor and set frequency in Pr 72 PWM frequency selection according to wiring length Limiting the voltage rise speed of the frequency inverter output voltage dU dT If the motor requires a rise speed of 500V µs or less you must install a filter in the output of the inverter Please contact your Mitsubishi dealer for more details 3 ...

Страница 14: ...ignals are micro currents Do not apply a voltage to the contact input terminals e g STF of the control circuit Always apply a voltage to the alarm output terminals A B C via a relay coil lamp etc It is recommended to use the cables of 0 3mm to 0 75mm gauge for connection to the control circuit terminals If the cable gauge used is 1 25mm or more the front cover may be lifted when there are many cab...

Страница 15: ...r arrester to be damaged If any of the above devices is installed immediately remove it Before starting wiring or other work after the inverter is operated wait for at least 10 minutes after the power supply has been switched off and check that there are no residual voltage using a tester or the like The capacitor is charged with high voltage for some time after power off and it is dangerous A sho...

Страница 16: ...city to have enough allowance for current Make sure that the specifications and rating match the system requirements A motor with encoder is necessary for vector control In addition connect the encoder directly to the backlash free motor shaft An encoder is not necessary for real sensorless vector control When the motor speed is unstable due to change in the frequency setting signal caused by elec...

Страница 17: ...t and consider the backup system such as checking up as below according to the level of importance of the system Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector Note that the motor current runs as the motor is running for the p...

Страница 18: ...njection brake operation frequency 0 to 120Hz 9999 3Hz 11 DC injection brake operation time 0 to 10s 8888 0 5s 12 DC injection brake operation voltage 0 to 30 4 2 1 13 Starting frequency 0 to 60Hz 0 5Hz 14 Load pattern selection 0 to 5 0 15 Jog frequency 0 to 400Hz 5Hz 16 Jog acceleration deceleration time 0 to 3600 360s 0 5s 17 MRS input selection 0 2 4 0 18 High speed maximum frequency 120 to 40...

Страница 19: ...mode selection 0 1 2 3 4 6 7 0 80 Motor capacity 0 4 to 55kW 9999 9999 81 Number of motor poles 2 4 6 8 10 12 14 16 18 20 9999 9999 82 Motor excitation current 0 to 500A 9999 9999 Parameter Name Setting Range Initial Value 83 Rated motor voltage 0 to 1000V 400V 84 Rated motor frequency 10 to 120Hz 60Hz 89 Speed control gain magnetic flux vector 0 to 200 9999 9999 90 Motor constant R1 0 to 50Ω 9999...

Страница 20: ... 106 108 110 4 145 PU PU display language selection 0 to 7 1 Parameter Name Setting Range Initial Value 148 Current detection Stall prevention level at 0V input 0 to 220 150 149 Stall prevention level at 10V input 0 to 220 200 150 Output current detection level 0 to 220 150 151 Output current detection signal delay time 0 to 10s 0s 152 Zero current detection level 0 to 220 5 153 Zero current detec...

Страница 21: ...00 100 243 Terminal 1 added compensation amount terminal 4 75 244 Cooling fan operation selection 0 1 1 Parameter Name Setting Range Initial Value 245 Slip compensation Rated slip 0 to 50 9999 9999 246 Slip compensa tion time con stant 0 01 to 10s 0 5s 247 Constant power range slip com pensation selec tion 0 9999 9999 250 Stop selection 0 to 100s 1000 to 1100s 8888 9999 9999 251 Output phase loss ...

Страница 22: ... waiting time setting 0 to 150ms 9999 9999 338 Communication operation com mand source 0 1 0 339 Communication speed command source 0 1 2 0 340 Communication startup mode selection 0 1 2 10 12 0 Parameter Name Setting Range Initial Value 341 RS 485 communication RS 485 commu nication CR LF selection 0 1 2 1 342 Communication EEPROM write selection 0 1 0 343 Communication error count 0 350 2 Orient...

Страница 23: ... Range Initial Value 450 Second motor constants Second applied motor 0 to 8 13 to 18 30 33 34 40 43 44 50 53 54 9999 9999 451 Second motor control method selection 10 11 12 20 9999 9999 453 Second motor capacity 0 4 to 55kW 9999 9999 454 Number of sec ond motor poles 2 4 6 8 10 9999 9999 455 Second motor excitation cur rent 0 to 500A 9999 9999 456 Rated second motor voltage 0 to 1000V 400V 457 Rat...

Страница 24: ...eter for manufacturer setting Do not set 548 Parameter Name Setting Range Initial Value 549 Communication Protocol selec tion 0 1 0 550 NET mode opera tion command source selection 0 1 9999 9999 551 PU mode opera tion command source selection 1 2 2 555 Current average value monitor Current average time 0 1 to 1 0s 1s 556 Data output mask time 0 0 to 20s 0s 557 Current average value monitor signal ...

Страница 25: ...que control inte gral time 2 0 to 500ms 9999 9999 836 Torque setting filter 2 0 to 5s 9999 9999 837 Torque detection filter 2 0 to 0 1s 9999 9999 Parameter Name Setting Range Initial Value 840 2 Torque bias Torque bias selection 0 to 3 9999 9999 841 2 Torque bias 1 600 to 1400 9999 9999 842 2 Torque bias 2 843 2 Torque bias 3 844 2 Torque bias filter 0 to 5s 9999 9999 845 2 Torque bias oper ation ...

Страница 26: ...e 0 1 to 1000h 9999 9999 898 Power saving cumulative moni tor clear 0 1 10 9999 9999 899 Operation time rate estimated value 0 to 100 9999 9999 Parameter Name Setting Range Initial Value C0 900 3 FM terminal calibration C1 901 3 AM terminal calibration C2 902 3 Terminal 2 frequency setting bias frequency 0 to 400Hz 0Hz C3 902 3 Terminal 2 frequency setting bias 0 to 300 0 125 903 3 Terminal 2 freq...

Страница 27: ...Setting Range Initial Value 990 PU buzzer control 0 1 1 991 PU contrast adjustment 0 to 63 58 Pr CL Parameter clear 0 1 0 ALLC All parameter clear 0 1 0 Er CL Faults history clear 0 1 0 Pr CH Parameter copy 0 1 2 3 0 Parameter Name Setting Range Initial Value 1 Differ according to capacities 7 5K or less 11K or more 2 Setting can be made only when the FR A7AP is mounted 3 The parameter number in p...

Страница 28: ...t be determined prior to switching on again as a recurrence of such faults at short intervals can lead to premature aging of components or even the complete breakdown of the device After the cause of the fault has been found and corrected the inverter can be reset and operations continue Inverter fault or alarm indications are roughly divided as below Error Message A message regarding operational ...

Страница 29: ...c thermal relay function E FIN Fin overheat E IPF Instantaneous power failure E UVT Undervoltage E ILF Input phase failure E OLT Stall prevention E GF Output side earth ground fault overcurrent E LF Output phase loss E OHT External thermal relay operation to to Fault E PTC PTC thermistor operation E OPT Option alarm E OP3 Communication option alarm to E 1 to E 3 Option fault E PE Parameter storage...

Страница 30: ...rth Connect the equipment to the earth securely Wire the earth terminal independently Do not connect two or more cables to one terminal Use the cable sizes on page 6 at the ambient temperature indicated there If the ambient temperature is different select appropriate wire according to EN60204 ANNEX C TABLE 5 When tightening the screw be careful not to damage the threads For use as a product compli...

Страница 31: ...more than 5 kA rms symmetrical amperes 528 V maximum FR A741 K 5 5 7 5 11 15 018 5 22 30 37 45 55 Rated voltage V 480V or more Fuse maximum allowable rating A 40 70 80 90 110 150 175 200 250 300 CAUTION Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input Avoid unnecessary reset and power off When multiple motors are operated by a single ...

Страница 32: ...codes For installation in Canada branch circuit protection must be provided in accordance with the Canada Electrical Code and any applicable provincial codes As specified UL Class T fuses or any faster acting fuse with the appropriate rating must be employed Maximum allowable rating by US National Electrical Code Exact size must be chosen for each installation A 2 3 Short circuit ratings Suitable ...

Страница 33: ...by inverter power reset and reset signal input Avoid unnecessary reset and power off When multiple motors are operated by a single inverter protection cannot be provided by the electronic thermal relay function Install an external thermal relay to each motor When the difference between the inverter and motor capacities is large and the setting is small the protective characteristics of the electro...

Страница 34: ...28 APPENDIX ...

Страница 35: ......

Страница 36: ...35 Riga Phone 371 0 784 2280 Fax 371 0 784 2281 LITHUANIA Beijer Electronics UAB Savanoriu Pr 187 LT 02300 Vilnius Phone 370 0 5 232 3101 Fax 370 0 5 232 2980 EUROPEAN REPRESENTATIVES MOLDOVA INTEHSIS srl bld Traian 23 1 MD 2060 Kishinev Phone 373 0 22 66 4242 Fax 373 0 22 66 4280 NETHERLANDS Koning Hartman b v Haarlerbergweg 21 23 NL 1101 CH Amsterdam Phone 31 0 20 587 76 00 Fax 31 0 20 587 76 05...

Отзывы: