Wiring
Connection of motor with encoder (vector control)
FR-A700 EC
3 - 41
Instructions for encoder cable wiring
Use twisted pair shield cables (0.2mm² or larger) to connect the FR-A7AP and position detector.
Cables to terminals PG and SD should be connected in paralell or be larger in size according to
the cable length.
To protect the cables from noise, run them away from any source of noise (e.g. the main circuit
and power supply voltage).
When differential line driver is set and a wiring length is 30m or more:
The wiring length can be extended to 100m by slightly increasing the power by 5V (approx.
5.5V) using six or more cables with gauge size of 0.2mm² in parallel or a cable with gauge
size of 1.25mm² or more. Note that the voltage applied should be within power supply
specifications of encoder.
To reduce noise of the encoder cable, earth (ground) the encoder shielded cable to the enclos-
ure (as near as the inverter) with a P clip or U clip made of metal.
Wiring Length
Paralell Connection
Larger-Size Cable
≤
10m
At least 2 cables
Cable gauge 0.2mm²
≥
0.4mm²
≤
20m
At least 4 cables
≥
0.75mm²
≤
100m
At least 6 cables
≥
1.25mm²
Tab. 3-19:
Cable gauges and number of paralell cables
Fig. 3-31:
Earthing (grounding) example using a P clip
I001448E
NOTE
For details of the optional encoder dedicated cable (FR-JCBL), refer to page 3-37.
Encoder cable
Shield
P clip
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......