Causes and corrective actions
Troubleshooting
7 - 14
Operation Panel
Indication
E.IPF
FR-PU04
FR-PU07
Inst. Pwr. Loss
Name
Instantaneous power failure protection
Description
If a power failure occurs for longer than 15ms (this also applies to inverter input shut-off),
the instantaneous power failure protective function is activated to stop the inverter output in
order to prevent the control circuit from malfunctioning. If a power failure persists for longer
than 100ms, the alarm warning output is not provided, and the inverter restarts if the start
signal is on upon power restoration. (The inverter continues operating if an instantaneous
power failure is within 15ms.) In some operating status (load magnitude, acceleration/
deceleration time setting, etc.), over current or other protection may be activated upon
power restoration.
When instantaneous power failure protection is activated, the IPF signal is output. (Refer to
section 6.16.)
Check point
Find the cause of instantaneous power failure occurrence.
Corrective action
앫
Remedy the instantaneous power failure.
앫
Prepare a backup power supply for instantaneous power failure.
앫
Set the function of automatic restart after instantaneous power failure (Pr. 57). (Refer to
section 6.16.1.)
Operation Panel
Indication
E.BE
FR-PU04
FR-PU07
Br. Cct. Fault
Name
Brake transistor alarm detection/internal circuit error
Description
This function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged
brake transistors.
In this case, the inverter must be powered off immediately.
Check point
앫
Reduce the load inertia.
앫
Check that the frequency of using the brake is proper.
Corrective action
Replace the inverter.
Operation Panel
Indication
E.UVT
FR-PU04
FR-PU07
Under Voltage
Name
Under voltage protection
Description
If the power supply voltage of the inverter reduces, the control circuit will not perform nor-
mal functions. In addition, the motor torque will be insufficient and/or heat generation will
increase. To prevent this, if the power supply voltage reduces below about 300V for the
400V class, this function stops the inverter output.
When a jumper is not connected across P/+-P1, the under voltage protective function is
activated.
When undervoltage protection is activated, the IPF signal is output. (Refer to section 6.16.)
Check point
1) Check for start of large-capacity motor.
2) Check that a jumper or DC reactor is connected across terminals P/+-P1.
Corrective action
1) Check the power supply system equipment such as the power supply.
2) Connect a jumper or DC reactor across terminals P/+-P1.
3) If the problem still persists after taking the above measure, please contact your sales
representative.
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......