Operation
Operation panel FR-DU07
FR-A700 EC
4 - 13
4.3.10
Parameter copy an parameter verification
PCPY Setting
Description
0
Cancel
1
Copy the source parameters to the operation panel.
2
Write the parameters copied to the operation panel into the destination inverter.
3
Verify parameters in the inverter and operation panel.
Tab. 4-2:
Setting of parameter PCPY
NOTES
When the copy destination inverter is not the FR-A700 series or parameter copy write is per-
formed after parameter read is stopped,"model error (rE4)" is displayed.
Refer to the extended parameter list Tab. 6-1 for availability of parameter copy.
When the power is turned off or an operation panel is disconnected, etc. during parameter
copy write, perform write again or check the values by parameter verification.