11.2 Q & A 

 

 General 

To what degree of overvoltage and overcurrent does the unit withstand? Is it necessary to connect a protective circuit 
out of the unit? 

Instantaneous

Up to 20 times the rated current and up to twice the rated voltage 

*

 Instantaneous: Current is applied 9 

times for 0.5 sec at intervals of 1 min and once for 5 sec. 

Continuous 

:  Up to 1.1 times the rated current and rated voltage 

 

 

Can this unit be used as a watt-hour meter? 

The unit can be used to measure the electric energy and control the consumption of electric energy. 
However, it should not be used for the purpose of trading or certification of electric energy regulated by Measurement Law. 

 

 

Is it easy to check for wiring failures? 

Check the state of measurement of electric energy. 

If MEASURE LED on the front panel of the main body (

see page 5) is on, the electric energy is being measured. Make sure 

that the electric energy value is approximate to the value obtained by the following formula to confirm more reliably that the unit is 
wired correctly. 

×

 current 

×

 voltage 

×

 (0.8 to 1.0) 

 

 

Is it secure to open the secondary terminal of the current sensor? 

The secondary side of each of Models EMU2-CT5 (-4W), EMU-CT50, EMU-CT100 and EMU-CT250 has a built-in protective 
circuit against opening of the secondary terminal. No problem occurs by opening the terminal during wiring work. However, for 
safety, do not continuously apply current while the terminal is open. 
Although the secondary side of each of Models EMU-CT400 and EMU-CT600 has a built-in protective circuit against opening of 
the secondary terminal, keep the secondary short-circuiting switch of the product in “Short” during wiring work. After the 
completion of the work, set the secondary short-circuiting switch to “Open.” If the switch is not set to “Open,” measurement will not 
be performed correctly. 

 

 

When a load, such as a welder, is used, current flows into the unit for only a short time (for example, 2 cycles). Can it 
measure the current correctly? 

This unit measures the parameters in a sampling period of 4340 Hz (at 50 and 60 Hz). 
The display updating period for display of measurement results on the display unit (EMU2-D65 or EMU2-D65-M) and the updating 
period for communication data output through communication, such as CC-Link, are 500 msec at the shortest. 
To determine the electric quantities, such as current, voltage, electric power, power factor, frequency, high-frequency voltage and 
high-frequency current, the results of measurement in a 500 msec period are processed by 2 second moving-average method (to 
be concrete, the moving average of four measurements obtained in a 500 msec period is calculated). Therefore, the mean values 
of these parameters are displayed. The maximum and minimum values of these electric parameters are calculated from the mean 
values. Accordingly, the unit cannot measure the instantaneous current correctly. 
The electric energy (integrated value) is continuously measured in a sampling period of 4340 Hz without intermission of 
measurement by processing separately from the above-mentioned instantaneous data processing. Therefore, the unit can 
measure the load in a short period. 

 

 

The measurements obtained by this unit differ from those obtained by another instrument. Why? 

There are various possible causes. Check the following points. 

1

  Check the wiring (particularly the polarity of the current sensor and connection of the voltage circuit). 

2

  Check that the parting faces of the split type current sensor are engaged without gaps and are not separated. 

3

  Check that there is no foreign matter between the parting faces of the split type current sensor. 

 

 Q&A relating to specifications 

To what is the measurement accuracy designed? 

For the electric energy, the measurement accuracy indicates the allowable range of error of readings. When the reading is 10 
kWh, the error is 

±

0.2 kWh. For the measuring parameters other than the electric energy, the measurement accuracy indicates 

the allowable ranges of error for the rating input. When the rated current is set to 250 A, the allowable range for current is 250 A 

±

 1%. 

 

 

Is the accuracy of the current sensor included? 

The accuracy of the current sensor is not included in the accuracy of this unit. 
The maximum allowable error is the sum of the allowable error of this unit and the error of the current sensor. 

 

 

To what range is minute current measured? 

The measurement of current is indicated starting from the range in which the current exceeds 0.5% of the rated current. In the 
range in which the current is less than 0.5% of the rated current, the measurement result is indicated as 0. However, also in this 
range, the electric energy is measured. Even when the indicated value of current is 0, the measurement of electric energy will 
increase if such a condition lasts for a long time. 

The electric energy is measured at a load of about 0.4% or more of the full-load power. 

Содержание EcoMonitorPro EMU2-RD2-C-4W

Страница 1: ...ctly operate the unit Page of related information Confirmation of contents of package Each unit comes with the following accessories Check for missing ones The accessories vary depending on the model Item Quantity Figure Main Body 1 EMU2 RD3 F EMU2 RD5 F EMU2 RD7 F EMU2 RD3 C EMU2 RD5 C EMU2 RD7 C EMU2 RD2 F 4W EMU2 RD4 F 4W EMU2 RD2 C 4W EMU2 RD4 C 4W Instruction manual Detailed edition CD 1 Inst...

Страница 2: ...wire breaking and contact failure z Tighten the screws to the specified torque 0 49 to 0 78 N m Excessive tightening can damage the terminals and screws z After tightening be sure to check that all screws have been tightened Failure to tighten any screw can cause unit malfunction fire or electric shock Connection with current sensor z Use this product in combination with the dedicated current sens...

Страница 3: ...spection 1 Check the product for damage 2 Check for abnormal indication of LED lamps 3 Check for abnormal noise odor and heat generation 4 Check for loose fittings and loose wires on the terminal block Perform the check stated in 4 in the power off state Failure to do so can cause electric shock unit failure or fire 3 6 Instructions for storage z When storing the unit turn off power disconnect cab...

Страница 4: ...13 Demand time limit 13 Upper and lower limit settings 14 10 Operations of Instrument 17 10 1 Measuring functions 17 10 2 Monitoring function 18 10 3 How to use the monitoring function 19 10 4 Resolution of measuring data 20 Voltage and harmonic voltage RMS 20 Current current demand and harmonic current RMS 20 Harmonic distortion rate 20 Power factor 20 Frequency 20 10 5 Restrictions on measuring ...

Страница 5: ...de Circuit 1 Circuit 2 SENSOR A Circuit 3 SENSOR B Circuit 4 SENSOR A Circuit 5 SENSOR B Circuit 6 SENSOR A Circuit 7 SENSOR B Example Model EMU2 RD4 C 4W DISPLAY Connect the display unit cable SENSOR SENSOR A SENSOR B Connect the connector of the dedicated current sensor cable P0 P1 P2 P3 Input voltage of the measuring circuit FG Keep the FG terminal grounded during practical use Caution When per...

Страница 6: ...and connected by experts in electrical work Applicable IEC rail 35 mm Installation Removal Fit the IEC rail with M4 or M5 screws at distances of 25 to 100 mm When connecting some rails secure both ends with slide preventive fittings When installing the unit after once it was removed from the IEC rail install it while pushing the IEC rail fitting upward Hang Push Pull up Pull the IEC rail fitting d...

Страница 7: ...Circuit 2 3 phase 3 wire system primary voltage 440 V primary current 250 A A 440 V 110 V potential transformer is separately necessary Circuit 3 Not used Circuit 4 Single phase 2 wire system primary voltage 110 V primary current 50 A Circuit 5 Single phase 3 wire system primary voltage 110 V primary current 100 A Circuit 6 3 phase 3 wire system primary voltage 2200 V primary current 400 A A 2200 ...

Страница 8: ...y necessary Circuit 2 primary voltage 63 5 110V primary current 250 A EMU CT250 Circuit 3 primary voltage 254 440V primary current 600 A EMU CT600 V 3 110 3 440 potential transformer is separately necessary Circuit 4 primary voltage 254 440V primary current 1000 A EMU2 CT5 4W V 3 110 3 440 potential transformer and 1000 5A current transformer are separately necessary EMU2 CT5 4W AC100 220V 0 1 2 3...

Страница 9: ... length is up to 10 5 m z Use EMU2 CB T MS when the side 1 is installed at a distance from the side 3 2 Connect the extension cables EMU2 CB T MS Brown Blue White White Fitting of EMU2 CT5 4W Fit the sensor to the cable of the circuit to be measured in accordance with the following procedures 1 Slide the lock pin in the arrow direction 2 Pass the electric wire into the clamp and close the clamp 3 ...

Страница 10: ...r less 38 mm2 or less 150 mm2 or less Fitting of EMU CT400 CT600 Fit the sensor to the cable of the circuit to be measured in accordance with the following procedures 1 Remove the band 1 in the arrow upward direction and remove the core cover 2 Remove the terminal cover and set the secondary short circuiting switch to Short 3 Loosen the screw 2 open the core band and remove the core Take care that...

Страница 11: ...mmunication line use a dedicated line and ensure that the total wiring distance station to station distance and terminal resistance are appropriate to B RATE If a dedicated line is not used or any wiring requirement is not met normal communication may not be made For the dedicated line and wiring requirements see the instruction manual for CC Link master unit z It is necessary to fit the terminal ...

Страница 12: ...thin slotted screwdriver z The relationship between the transmission rate and the setting switch is shown below Transmissio n rate 156k 625k 2 5M 5M 10M Setting If the switch is set to a state not shown above an error occurs 3 If the station number and or the transmission rate are is set or changed after power is applied to the unit press the reset switch z If the reset switch is not pressed the s...

Страница 13: ...250A 300A 400A 500A 600A 750A 800A 1000A 1200A 1500A 1600A 2000A 2500A 3000A 4000A 5000A 6000A 7500A 8000A 10000A 12000A 20000A 25000A 30000A Caution EMU CT50 EMU CT100 EMU CT250 EMU CT400 and EMU CT600 are designed for low voltage circuits maximum voltage of 460 V These models are not applicable to high voltage circuits When using EMU2 CT5 pass the secondary side 5A of the current transformer thr...

Страница 14: ...er limit setting Setting step Max upper lower limit setting 110 V to 220 V 0 0 V 0 1 V 440 V to 2200 V 0 V 1 V 3300 V to 110000 V 0 V 10 V Rated primary voltage setting 15 11 Power demand upper lower limit setting Full load power kW Min upper lower limit setting Setting step Max upper lower limit setting Less than 12 0 000 kW 0 001 kW 12 to less than 120 0 00 kW 0 01 kW 120 to less than 1200 0 0 k...

Страница 15: ... to 200 V maximum voltage of 260 V Connecting it to a high voltage circuit by mistake may cause burnout of the unit or a fire resulting in a hazardous situation Supplementation z When EMU2 CT5 4W is used set the ratings of the primary CT Demand time limit Default 2 min The current demand time limit and the power demand time limit can be set separately One of the following settings of each item can...

Страница 16: ...value and date and time of occurrence Initialize Initialize Initialize Initialize Initialize Current Instantaneous total Initialize Initialize Initialize Demand current Instantaneous max min Initialize Initialize Initialize Initialized when setting for current is changed Voltage Instantaneous max min total Initialize Initialize Electric power Instantaneous Initialize Initialize Initialize Initiali...

Страница 17: ...nce of max and min Current value of electric power Current value Maximum Minimum Power demand The moving average in the specified time limit is indicated Date and time of occurrence of max and min Reactive power Current value Maximum Minimum Power factor Date and time of occurrence of max and min Frequency R S High frequency current total effective value distortion factor T Note 1 R S S T Note 1 H...

Страница 18: ... VS T and VT R Single phase 3 wire Smaller value of VR S or VT R 3 phase 3 wire Smallest value of VR S VS T and VT R Minimum voltage 3 phase 4 wire Smallest value of VR S VS T and VT R 10 2 Monitoring function The parameters to be monitored are shown in the following table Monitoring item Detail Value upon occurrence Current demand upper lower limit alarm Date and time of occurrence Value upon occ...

Страница 19: ...ment Lower limit setting Monitoring data Alarm status Indicates whether the alarm has occurred or not Value upon occurrence of alarm Value upon occurrence of the alarm when condition of occurrence of alarm was met not the maximum value Date and time of occurrence of alarm Date and time when the alarm occurred condition of occurrence of alarm was met Example of current demand upper limit alarm Exam...

Страница 20: ...reactive power electric energy and reactive power energy Single phase 2 wire Single phase 3 wire 3 phase 3 wire 3 phase 4 wire Primary voltage setting W var 3rd decimal place Wh varh 2nd decimal place W var 1st decimal place Wh varh Integer W var Integer Wh varh 10 Primary current setting A Primary current setting A W var 3rd decimal place Wh varh 2nd decimal place W var 2nd decimal place Wh varh ...

Страница 21: ...age to this unit is 160 V or less 0 Hz is displayed In the case of other setting When the input voltage to this unit is 80 V or less 0 Hz is displayed Measurement incompletion error error code 17h is returned Frequency Frequency condition When the frequency is less than 44 5 Hz 44 5 Hz is displayed as a fixed value When the frequency exceeds 66 5 Hz 66 5 Hz is displayed as a fixed value Same as on...

Страница 22: ...en a minus value is displayed z Make sure that the terminals K and L of the current sensor are connected correctly z Make sure that the current line is passed through the current sensor in the correct direction Check the arrow direction printed on the nameplate the arrow mark from the power supply side to the load side 3 Connect only the side 3 of the current sensor and check the indication as sta...

Страница 23: ... current voltage electric power power factor frequency high frequency voltage and high frequency current the results of measurement in a 500 msec period are processed by 2 second moving average method to be concrete the moving average of four measurements obtained in a 500 msec period is calculated Therefore the mean values of these parameters are displayed The maximum and minimum values of these ...

Страница 24: ...hould attention be given for correct wiring A Check the polarity of the primary current of the current sensor K and L are shown on the power supply side and the load side of the circuit respectively An arrow mark is shown in the direction from K to L In the case of a 3 wire circuit check that the current sensor is connected to this unit without misconnection on the sides 1 and 3 Check that the vol...

Страница 25: ... capacitor Compensation for power failure Clock backup time Accumulated time of power failure Approx 168 hours at 25 C Note 3 The clock is initialized 12 00 on Jan 1 2003 when the accumulated time exceeds the setting Clock accuracy Note 4 Approx 1 min month Sensor cable Use of dedicated cable optional Connection to sensor Wiring length to current sensor For split type 5A sensor Extension of 10 m 1...

Страница 26: ...licable electric wire and applicable crimp type terminal terminal block Applicable electric wire 1 25 mm 2 Applicable crimp type terminal Terminal 7 2 mm or less in diameter for M3 5 Ex R1 25 3 5 bare round type ...

Страница 27: ... EMU2 RD2 C 115 97 98 EMU2 RD4 C 152 5 97 98 Expected product life 10 years Note 1 110 V and 220 V circuits can be connected directly An external potential transformer is necessary for circuits of 440 V or more Note 2 When the 5A sensor is used the primary current can be set to the following values 5A 6A 7 5A 8A 10A 12A 15A 20A 25A 30A 40A 50A 60A 75A 80A 100A 120A 150A 200A 250A 300A 400A 500A 60...

Страница 28: ...ng cables For CC Link connection use the specified cables The terminal resistance varies depending on the type of the dedicated cable For the details of the dedicated cables and terminal resistance see the manual supplied with the master unit 13 Peripheral Devices The following products are available Product name Model Remarks EMU CT50 50A Split type sensor EMU CT100 100A Split type sensor EMU CT2...

Страница 29: ...nsions Unit mm Model name L1 L2 EMU2 RD3 F EMU2 RD2 F 4W 86 75 EMU2 RD5 F EMU2 RD4 F 4W 123 5 112 5 EMU2 RD7 F 161 150 Model name L1 L2 EMU2 RD3 C EMU2 RD2 C 4W 111 100 EMU2 RD5 C EMU2 RD4 C 4W 148 5 137 5 EMU2 RD7 C 186 175 ...

Страница 30: ...2 5 22 24 Core cover M4 screw Terminal cover Secondary short circuiting switch Secondary terminal M4 screw Iron core parting face EMU2 CT5 EMU2 CT5 4W Details of sensor Dedicated cable EMU2 CB1 DR EMU2 CB1 DR 4W EMU2 CB T M EMU2 CB T MS 6 core cable Model Size L EMU2 CB T1M 1000 EMU2 CB T1M 5000 EMU2 CB T10M 10000 EMU2 CB T20M 20000 3 core cable Pair of two cables Model Size L EMU2 CB T1MS 1000 EM...

Страница 31: ...nction 19 I IEC rail fitting 6 Installation 6 L LED ALARM 5 L ERR 5 L RUN 5 MEASURE 5 RD 5 RUN 5 SD 5 Lower limit 14 15 M MA MB 5 Monitoring function 18 O Optional parts 30 P P0 P1 P2 P3 5 Part Names and Functions 5 Peripheral Devices 28 Phase and Wiring 13 15 Primary current 13 15 Primary voltage 13 15 Q Q A 23 R RESET 5 Resolution of measuring data 20 Restrictions on measuring data 21 S Safety p...

Страница 32: ...16 Bo Aung Gyaw Street Botataung 1161 Yangon Myanmar 95 0 1 202589 202449 202590 Nepal Watt Volt House Co Ltd KHA 2 65 Volt House Dllli Bazar Post Box 2108 Katmandu Nepal 977 1 411330 Pakistan Prince Electric Co 16 Brandreth Road Lahore 54000 Pakistan 92 0 42 7654342 Philippines EDISON ELECTRIC INTERGRATED INC 24th Fl Galleria Corporate Center Edsa Cr Ortigas Ave uezon City Metro Manila Philippine...

Отзывы: