EcoDan Installation Manual Version 1.0 (26/01/09) Ice Energy Heat Pumps Ltd © 2008
- 17 -
5 KW
Circuit Breaker size
16 Amp
Cable size
1.5mm
Maximum Running Current
13 Amp
Maximum Starting Current
3 Amp
9KW
Circuit Breaker size
25 Amp
Cable size
4mm
Maximum Running Current
23 Amp
Maximum Starting Current
5 Amp
14 KW
Circuit Breaker size
40 Amp
Cable size
6mm
Maximum Running Current
35 Amp
Maximum Starting Current
14 Amp