6-6. DIP Switch Functions
The DIP switch number is printed on the circuit board next to the relevant switch
-
es. The word ON is printed on the circuit board and on the DIP switch block itself.
To move the switch you need to use a pin or the corner of a thin metal ruler or
similar.
DIP switch settings are listed below in Table 6.6.1.
Only an authorised installer can change DIP switch setting under one’s own re
-
sponsibility according to the installation condition.
Make sure to turn off both indoor unit and outdoor unit power supplies before
changing the switch settings.
DIP switch
Function
OFF
ON
Default settings:
Indoor model name
SW1 SW1-1 Boiler
WITHOUT Boiler
WITH Boiler
OFF
SW1-2
Heat pump maximum outlet water temperature
55ºC
60ºC
ON
*1
SW1-3 DHW tank
WITHOUT DHW tank
WITH DHW tank
OFF
SW1-4 Immersion heater
WITHOUT Immersion heater
WITH Immersion heater
OFF
SW1-5 Booster heater
WITHOUT Booster heater
WITH Booster heater
OFF: E***-M*D
ON : E***-*M2/6/9*D
SW1-6 Booster heater function
For heating only
For heating and DHW
OFF: E***-M*D
ON : E***-*M2/6/9*D
SW1-7 Outdoor unit type
Split type
Packaged type
OFF: Except E*PX-*M**D
ON : E*PX-*M**D
SW1-8 Wireless remote controller
WITHOUT Wireless remote controller WITH Wireless remote controller
OFF
SW2 SW2-1 Room thermostat1 input (IN1) logic change
Zone1 operation stop at thermostat short Zone1 operation stop at thermostat open OFF
SW2-2
Flow switch1 input (IN2) logic change
Failure detection at short
Failure detection at open
OFF
SW2-3 Booster heater capacity restriction
Inactive
Active
OFF: Except E***-VM2*D
ON : E***-VM2*D
SW2-4 Cooling mode function
Inactive
Active
OFF: Except ER**-*M**D
ON
: ER**-*M**D
SW2-5
Automatic switch to backup heat source operation
(When outdoor unit stops by error)
Inactive
Active
*2
OFF
SW2-6 Mixing tank
WITHOUT Mixing tank
WITH Mixing tank
OFF
SW2-7 2-zone temperature control
Inactive
Active
*3
OFF
SW2-8
Flow sensor
WITHOUT Flow sensor
WITH Flow sensor
ON
SW3 SW3-1 Room thermostat 2 input logic change
Zone2 operation stop at thermostat short Zone2 operation stop at thermostat open OFF
SW3-2
Flow switch 2 and 3 input logic change
Failure detection at short
Failure detection at open
OFF
SW3-3
—
—
—
OFF
SW3-4 Electric energy meter
WITHOUT Electric energy meter
WITH Electric energy meter
OFF
SW3-5 Heating mode function
*4
Inactive
Active
ON
SW3-6
2-zone valve ON/OFF control
Inactive
Active
OFF
SW3-7 Heat exchanger for DHW
Coil in tank
External plate HEX
OFF
SW3-8 Heat meter
WITHOUT Heat meter
WITH Heat meter
OFF
SW4 SW4-1 Multiple outdoor units control
Inactive
Active
OFF
SW4-2 Position of multiple outdoor units control
*5
Sub
Main
OFF
SW4-3
—
—
—
OFF
SW4-4
Indoor unit only operation (during installation work)
*6
Inactive
Active
OFF
SW4-5 Emergency mode (Heater only operation)
Normal
Emergency mode (Heater only operation) OFF
*7
SW4-6 Emergency mode (Boiler operation)
Normal
Emergency mode (Boiler operation)
OFF
*7
SW5 SW5-1
DHW tank water temperature over heat protection (L4)
Active
Inactive
*8
OFF
SW5-2 Advanced auto adaptation
Inactive
Active
ON
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
SW5-8
—
—
—
OFF
SW6 SW6-1
—
—
—
OFF
SW6-2
—
—
—
OFF
SW6-3 Pressure sensor
Inactive
Active
OFF: Except E*SD-*M**D
ON : E*SD-*M**D
SW6-4 Analog output signal (0 to 10V)
Inactive
Active
OFF
SW6-5
—
—
—
OFF
<Table 6.6.1>
<Figure 6.6.1>
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
E*SC-*M**D
ON
ON
ON
ON
OFF
E*SD-*M**D
ON
OFF
OFF
ON
OFF
E*SE-*M*ED
OFF
ON
ON
OFF
ON
E*PX-*M**D
OFF
OFF
OFF
OFF
OFF
Capacity code
Notes:
*1
. When the hydrobox is connected with a PUMY-P outdoor unit of which maximum outlet water temperature is 55ºC, DIP SW1-2 must be changed to OFF.
*2
. OUT11 will be available. For safety reasons, this function is not available for certain errors. (In that case, system operation must be stopped
and only the water circulation pump keeps running.)
*3
. Active only when SW3-6 is set to OFF.
*4
. This switch functions only when the hydrobox is connected with a PUHZ-FRP outdoor unit. When another type of outdoor unit is connected,
the heating mode function is active regardless of the fact that this switch is ON or OFF.
*5
. Active only when SW4-1 is set to ON.
*6
. Space heating and DHW can be operated only in indoor unit, like an electric heater. (Refer to "Indoor unit only operation” in page 42. )
*7
. If emergency mode is no longer required, return the switch to OFF position.
*8
. Please make sure to have necessary overheat protection on locally supplied solar thermal system side to secure safety, as the tank tem-
perature could be much higher (than current).
SW1
SW3
SW4
SW2
SW5
SW6
OCH712C